22
All of the conditions below must be met!:
1. The device is in error! (No AC output)
2. Inverter LED flashes (in opposition to any flashing of the Bulk, Absorption or Float LED)
3. At least one of the LEDs Bulk, Absorption and Float is on or flashing
Bulk LED off
Bulk LED flashes
Bulk LED on
Absorption LED
Absorption LED
Absorption LED
off
flashing
On
off
flashing
on
off
flashing
on
Float LED
off 0 3 6
Float LED
off 9 12 15
Float LED
off 18 21 24
flashing 1 4 7 flashing 10 13 16 flashing 19 22 25
on 2 5 8 on 11 14 17 on 20 23 26
Bulk LED
Absorption LED
Float LED
Code Meaning: Cause/solution:
1
Device is switched off because one of
the other phases in the system has
switched off.
Check the failing phase.
3
Not all, or more than, the expected
devices were found in the system.
The system is not properly configured. Reconfigure the system.
Communication cable error. Check the cables and switch all equipment off,
and then on again.
4 No other device whatsoever detected. Check the communication cables.
5 Overvoltage on AC-out. Check the AC cables.
10
System time synchronisation problem
occurred.
Should not occur in correctly installed equipment. Check the communication
cables.
14 Device cannot transmit data. Check the communication cables (there may be a short circuit).
17
One of the devices has assumed
‘master’ status because the original
master failed.
Check the failing unit. Check the communication cables.
18 Overvoltage has occurred. Check AC cables.
22 This device cannot function as ‘slave’. This device is an obsolete and unsuitable model. It should be replaced.
24 Switch-over system protection initiated.
Should not occur in correctly installed equipment. Switch all equipment off,
and then on again. If the problem recurs, check the installation.
25
Firmware incompatibility. The firmware
of one the connected devices is not
sufficiently up to date to operate in
conjunction with this device.
1) Switch all equipment off.
2) Switch the device returning this error message on.
3) Switch on all other devices one by one until the error message reoccurs.
4) Update the firmware in the last device that was switched on.
26 Internal error.
Should not occur. Switch all equipment off, and then on again. Contact
Victron Energy if the problem persists.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Victron energy MultiPlus 3000 and is the answer not in the manual?

Victron energy MultiPlus 3000 Specifications

General IconGeneral
BrandVictron energy
ModelMultiPlus 3000
CategoryInverter
LanguageEnglish

Related product manuals