The inverter has switched off due to
the electronics temperature being
too high.
-If the LEDs are flashing alternately,
the battery is nearly exhausted and
the nominal output is exceeded.
-If "overload" and "low battery" flash
simultaneously, the ripple voltage
on the battery terminals is too high.
The inverter switched off due to
excess ripple voltage on the battery
terminals.
The AC input voltage is switched
through and the charger operates in
bulk mode.
The mains voltage is switched
through and the charger is on.
The set absorption voltage,
however, has not yet been reached.
(BatterySafe mode)
The mains voltage is switched
through and the charger operates in
absorption mode.