EasyManua.ls Logo

Viessmann 47-819-55 - Filling the Heating System

Viessmann 47-819-55
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
Remove these 3 labels. Apply the labels in the follow-
ing positions:
■
For commissioning, affix a label to the place marked
on the type plate.
■
Affix a label in the space provided in the operating
instructions.
■
For later use, affix a label here:
Fig. 22
Switch on the WiFi connection. Establish a connection
to the router:
■
Information on WiFi: See chapter "WiFi operational
reliability and system requirements".
■
Establishing an internet connection
Operating instructions
Note
If "E10" is displayed, the connection to the home net-
work could not be established. Check the router and
the network password.
If "E12" is displayed, the connection to the server
could not be established. Re-establish the connection
at a later time.
Note
If the communication module is to be switched on or
off, press and OK simultaneously for 4 s.
Filling the heating system
Fill water
As a heat transfer medium for DHW heating, the heat-
ing water must meet fluid category ≤ 3. This require-
ment is met if water of potable quality is used as heat-
ing water. For example, if additives are used, the addi-
tive manufacturer must specify which category the
treated heating water comes under.
!
Please note
Unsuitable fill water increases the level of
deposits and corrosion and may lead to appli-
ance damage.
■
Flush the heating system thoroughly before
filling.
■
Only use fill water of potable water quality.
■
Special antifreeze suitable for heating systems
can be added to the fill water. The antifreeze
manufacturer must verify its suitability.
■
Fill and top-up water with a water hardness
above 300 ppm must be softened, e.g. with a
small softening system for heating water.
E D C A
1.
Fig. 23
Commissioning, inspection, maintenance
Commissioning the system (cont.)
6221465