Viessmann 47-819-55 - Fault Messages

Viessmann 47-819-55
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
63
A
B
Fig. 44
A
HBMU heat management unit
B
Programming unit with TCU 100 communication
module
Fault messages
Note
For diagnostics and troubleshooting, see chapter
"Repairs".
Fault messages dependent on appliance equipment
level
7
System characteristics
No DHW heating
Cause
Lead break, cylinder temperature sensor
Measures
■
Check DHW setting in the commissioning assistant
and correct if necessary.
■
Check the cylinder temperature sensor (terminal
S.T.S).
■
Measure the voltage at the sensor input on the
HBMU heat management unit. Set value: 3.3 V with
sensor disconnected
Replace faulty component if necessary.
Troubleshooting
Overview of electronics modules
6221465
Diagnosis
Viessmann 47-819-55 - Fault Messages