46
Danger
Contact with live components can lead to seri-
ous injury from electric current. Some compo-
nents on PCBs remain live even after the power
supply has been switched off.
■
Do not touch the wiring chambers (control
unit and mains connections).
■
When working on the appliance, isolate the
system from the power supply, e.g. at a sepa-
rate fuse or a main switch. Check the system
is no longer live and safeguard against recon-
nection.
■
Before working on the appliance, wait at
least 4 min until the voltage has completely
dropped out.
A
B
C
D
E
F
4x
19, 25 kW
E
E
F
4x
D
C
B
A
32 kW
1. Turn off the ON/OFF switch.
2. Close the gas shut-off valve and safeguard against
reopening.
3. Disconnect cables and leads from:
■
Fan motor
A
(2 plugs)
■
Ionisation electrode
B
■
Ignition unit
C
■
Earth
D
4.
Undo gas supply pipe fitting
E
.
5.
Undo 4 screws
F
and remove the burner.
Note
Cover gas connection
E
so that no small parts
can fall into it.
Commissioning, inspection, maintenance
Removing the burner
6221465