EasyManua.ls Logo

Viessmann ECV Series - Page 21

Viessmann ECV Series
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connections
21
Venting Connection (continued)
Vent terminal connection
The vent must be installed observing
local regulations in addition to National
Codes, CAN/CSA-B149.1 or 2, or ANSI
Z223.1. A vent shall not terminate:
1. directly above a paved sidewalk or
paved driveway which is located
between two single-family dwellings
and serves both dwellings;
2. less than 7 ft. (2.13 m) above a
paved sidewalk or a paved driveway
located on public property;
3. within 6 ft. (1.8 m) of a mechanical
air s upply inlet to any building
(clothes dryer vents and non-sealed
combustion furnace and hot water
heater vents should be considered to
be mechanical air inlets);
4. above a meter/regulator as sembly
within 3 ft. (900 mm) horizontally of
the vertical center-line of t he
regulator;
5. within 6 ft. (1.8 m) of any gas
service regulator vent outlet;
6. less than 1 ft. (300 mm) above grade
level or anticipated snow level
(consult local building authorities or
local weather office). Locate the v ent
terminal so that it cannot be blocked
by snow;
7. within the following distances of a
window or door which can be opened
in any building, any non-mechanical
air supply inlet to any building, or the
combustion inlet of any other
appliance:
i) 12 inches (300 mm) (CSA) for
inputs up to and including 100,000
Btu/h (30 kW). Note ANSI requires
4 ft. (1.22 m);
ii)3 ft. (1 m) (CSA) for inputs
exceeding 100,000 Btu/h (30 kW).
Note ANSI requires 4 ft. (1.22 m);
8. underneath a veranda, porch or deck;
9. within 6 ft. (1.8 m) of an inside
corner formed by 2 exterior walls;
10 ft. (3.0 m) or greater is
recommended where possible;
10. within 29” (736 mm) horizontally or
vertically from any soffit not
containing an air intake opening;
11. in areas where condensation may
cause problems, such as above
planters, patios, or adjacent to
windows where flue gases may
cause fogging;
12. within 3 ft. (1 m) to the property
line (advisable, not mandatory -
check with local building authorities
and municipal bylaws);
13. at a location where ice formation on
the ground can present a hazard;
14. so that the f lue gases are directed
towards brickwork, siding, or other
construction, in such a manner that
may cause damage from heat or
condensate from the flue gases ;
15. where discharging hot flue gases
may cause property damage or
personal injury.
5167 450 v1.4

Other manuals for Viessmann ECV Series

Related product manuals