Additional Information
45
Technical Data (continued)
Boiler Model
Model
No.
ECV-65 ECV-80 ECV-100 ECV-115 ECV-140 ECV-155 ECV-180 ECV-200
CSA input MBH
kW
65
19
80
23
100
29
115
34
140
41
155
45
180
53
200
58
CSA output
DOE heating capacity
MBH
kW
55
16
67
19
84
24
97
28
118
34
131
38
151
44
168
49
AFUE
*1
% 83.1 83.1 83.1 83.1 83.1 83.1 83.1 83.1
Steady state efficiency % 84.5 84.3 84.2 84.5 84.5 84.5 84.0 84.0
Total dimensions
Length
Width
Height
inches
mm
inches
mm
inches
mm
19¾
502
13½
340
39½
1003
19¾
502
13½
340
39½
1003
19¾
502
17
432
39½
1003
19¾
502
17
432
39½
1003
19¾
502
21
533
39½
1003
19¾
502
21
533
39½
1003
19¾
502
25
635
39½
1003
19¾
502
25
635
39½
1003
Total weight (incl.
insulation, burners and
packaging)
lbs
kg
243
110
243
110
295
133
295
133
365
165
365
165
432
195
432
195
Number of cast iron
sections
3 3 4 4 5 5
6
6
Number of burners 2 2 3 3 4 4 5 5
Water connection inches 1¼
Water content USG
ltr
2.6
9.9
2.6
9.9
3.5
13.2
3.5
13.2
4.3
16.5
4.3
16.5
7.1
26.8
7.1
26.8
Gas connection inches ½
Vent pipe collar outside
Ø”
3
*1
With intermittent pilot electronic ignition system and integrated power vent, Vitogas 050, ECV boilers exceed the
Canadian and U.S. minimum AFUE requirement of 80%.
All sizes available with propane gas. For net IBR rating divide output by 1.15. Electrical requirement: 120V, 60Hz, less than
12A.
For use with natural gas 1000 Btu/ft.
3
. kW figures are approximate.
Parts List for Honeywell Intermittent Pilot Ignition Sy stem
NATURAL GAS PROPANE GAS
GAS CONTROL LIST HONEYWELL PART NO. VIESSMANN PART NO. HONEYWELL PART NO. VIESSMANN PART NO.
Gas Valve VR8204M1133 9543730 VR8204M1133 9543730
LP Convers i on Kit 9543396
Ignition Control S8600M 7133567 S8600H 7134197
Pilot Burner Q3451A2012 7133473 Q3451A2012 7133473
Pilot Orifice .020 inches dia.
390686-4 BCR 20
9549687 .014 inches dia.
390696-24 BBR 14
9543392
Note: Do not use S8600M control (continuous trial for ignition) on propane gas.