Viessmann Vitodens 300 - Page 13

Viessmann Vitodens 300
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Yes
Differential pre s-
sure sensor
enables start
(0.75 V across
terminals X8.5
and X8.6)
No
After approx.
51 seconds
Check fan cables
and fan plug -in
connectio ns,
check fan
Fault
E6
Yes
Ignition
No
Fault Check the ig nition
module (contr ol
voltage 230 V
across plug s X2.1
and X2.2)
F4
Yes
Gas combinati on
valve opens
No
Fault Check the ga s
train (control vol -
tage 230 V) and
gassupplypres-
sure
F4
Yes
Ionisation cur-
rent build s
(higher t han
5µA)
No
Fault Check the io nisa-
tion current, the
electrode adjust-
ment and the gas
pipe for air locksSymbol A
F4
Yes
Operational bur-
ner
Stops below se t
boiler tempera-
ture and restarts
Check flue gas
system for sound-
ness (flue gas
recirculation),
check gas flow
pressur e
Further details regarding the individual steps (cont.)
13
Initial start-up, inspection, maintenance
5692 537 GB