Summary
Codes
Coding in
the as
delivered
condition
Address:
value
Function mode Coding
change
Address:
value
Possible change
System design
00:1 System design 1:
1heatingcircuitwithout
mixer A1, without DHW
heatin g
00:2 System design 1, 6:
1heatingcircuitwithout
mixer A1, with DHW heat-
ing
00:3 System design 5:
1 mixer circuit M2, with-
out DHW heating
00:4 System design 5:
1 mixer circuit M2, with
DHW heating
00:5 System design 2, 3, 4:
1heatingcircuitwithout
mixerA1and1mixercir-
cuit M2, without DHW
heatin g
00:6 System design 2, 3, 4:
1heatingcircuitwithout
mixer A1, 1 mixer circuit
M2 with DHW heating
Max. boiler temp.
06:... Maximum limit of the
boiler water tempera-
ture, defau lted by the
boiler coding card
06:20
to
06:127
Maximum limit of the boi-
ler water temperat ure
within the ranges
defaulted by the boile r
Gas type
1E:0 Operation with natural
gas
1E:1 Operation with LPG
Ve nting/filling
2F:0 Venting/filling program
disabled
2F:1 Venting program enabled
2F:2 Filling program enabled
Code 1 (cont.)
41
Coding
5692 537 GB