Coding in
the as
delivered
condition
Address:
value
Function mode Coding
change
Address:
value
Possible change
58:0 Without auxiliary func-
tion for DHW loading
58:1
to
58:95
Input of DHW set value 2;
adjustab le from 1 to
95 °C (observe coding
address 5 6)
59:0 DHW cylinder loading:
Starting point -2.5 K
Stoppin g point +2 .5 K
59:1
to
59:10
Starting poi nt adjustable
from1to10Kbelowthe
set value
5b:0 DHW cylinder directly
connected to t he boiler
5b:1 DHW cylinder connected
downstream of the low
loss header
60:20
*
1
During DHW loading,
the boiler water tem-
perature is up to 20 K
higher than the set
DHW temperature
60:5
to
60:25
Thedifferencebetween
the boiler water tempera-
ture and the set DHW
temperature is adjustable
from5to25K
62:2 Circulation pump with 2
minutes run-on time
after cylin der loading
62:0 Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from1to15minutes
63:0
*
2
Without auxiliary
function for DHW load-
ing
63:1 Additional function: 1 x
daily
63:2
to
63:14
Every 2 to every 1 4 da ys
63:15 2 x daily
65:... Information regarding
the type of diverter
valve (not adjustable)
65:0 Without diverter valve
65:1 Diverter valve by Viess-
mann
65:2 Diverter valve by Wilo
65:3 Diverter valve by Grund-
fos
67:40 In conjunction with Vito-
solic solar control unit -
set DHW value 3
67:0
to
67:60
DHW set value adjusta-
ble from 0 to 60 °C
Code 2 (cont.)
50
Coding
5692 537 GB
*1
Only for weather-compensated co ntrol u nits.
*2
Only for constant temperature control u nits.