Viessmann Vitopend 100-W - There is no hot water

Viessmann Vitopend 100-W
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
Display Action
Control unit issues
a heat demand
No
Increase set value
and ensure heat is
drawn off
Yes
Ignition
No
Fault "F4"
Check the ignition
module connec-
tion
Yes
Gas train opens
No
Fault "F4"
Check the gas
train (control volt-
age 230 V) and
gas supply pres-
sure
Yes
Ionisation current
builds (higher than
2 µA)
Symbol
A
No
Fault "F4"
Check the ionisa-
tion current, check
the electrode ad-
justment and the
gas line for air-
locks.
Yes
Burner in opera-
tion
No
Shuts down below
the set boiler water
temperature and
restarts immediate-
ly
Check the flue sys-
tem for tightness
(flue gas recircula-
tion); check the
gas flow pressure
Troubleshooting
Function sequence and possible faults
5848 649 GB
Service