Coding in the factory default setting Possible change
General (cont.)
A6 : 36 Extended economy circuit inactive A6 : 5
to
A6 : 35
Extended economy circuit active, i.e. the
heating circuit pump will be switched OFF,
and the mixing valve closed at a variable
value, which is adjustable between 5 to 35°C
plus 1°C / 41 to 95°F plus 2°F.
This value is based on the adjusted outdoor
temperature, comprising the actual outdoor
temperature and a time constant which takes
the cooling down of an average building into
consideration.
A7 : 0 Without mixing valve economy function A7 : 1 With mixing valve economy function (exten-
ded heating circuit pump logic)
Heating circuit pump can also OFF, if the mi-
xing valve has been closed for longer than 12
minutes.
The heating circuit pump is switched ON again
when the mixing valve goes to its control
mode
when there is a risk of freezing
A9 : 7
With pump idle period:
A0 : 0
Without pump idle period
modification (by changing the operating
mode or changes on the rotary dial ts or
key tm )
A9 : 1
to
A9 : 15
With pump idle period adjustable from 1 to 15
AA : 2 With LON communication module:
AA : 0 Without output reduction
sor aJA of the boiler control unit
AA : 1 Without function
b0 : 0 With remote control:
Heating mode/ red. mode:
weather-compensated
b0 : 1 Heating mode:
weather compensated
Red. mode:
with room temperature connection
b0 : 2 Heating mode:
with room temperature connection
Red. mode:
weather compensated
b0 : 3 Heating mode/ red. mode:
with room temperature connection
b2 : 8 With remote control unit and for the heating
b2 : 0 Without room influence
circuit, heating with room temperature control
must be coded
Room influence factor: 8
b2 : 1
to
b2 : 31
Room influence factor adjustable
from 1 to 31