48
Coding
Coding 2
(cont.)
Coding in the factory default setting Possible change
General (cont.)
F1 : 0 Slab curing function inactive F1 : 1
to
F1 : 4
Slab curing function adjustable in
accordance with four optional
temperature-time profiles
Please note!
Observe the slab curing suppliers
instructions.
The report to be provided by the
heating contractor must contain the
following heati-up details:
Heat-up data with respective
supply temperatures
Max. supply temperature reached
Operating status and outdoor
temperature during hand-over
The function is resumed after a
power failure or after the control
unit is switched OFF.
Heating program r will be started,
after the slab-curing function has
been completed or if the address is
manually set to 0.
F2 : 8 With remote control:
Time limit for party mode
F2 : 0
No time limit for party mode *
1
8 hours *
F2 : 1
to
F2 : 12
Time limit for party mode
adjustable from 1 to 12 hours
*
1
Party mode ends automatically with the heating program r when the system changes over to operation with standard room
temperature.
5285 967 v1.2