Mounting conditions
Mounting place - In the control cabinet
Mounting position - Horizontal and vertical
EMC Standard Comment
Emitted interfer-
ence
EN 61000-6-4 Class A (Industrial area)
Noise immunity
zone B
EN 61000-6-2 Industrial area
EN 61000-4-2
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity
2)
EN 61000-4-3 HF irradiation (casing)
80MHz … 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
EN 61000-4-6 HF conducted
150kHz … 80MHz, 10V, 80% AM (1kHz)
EN 61000-4-4 Burst, degree of severity 3
EN 61000-4-5 Surge, installation class 3 *
*) Due to the high-energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements like conductors
for lightning and overvoltage is necessary.
2.6 Technical data
2.6.1 62K-NHC0-DH
Order no. 62K-NHC0-DH
Type Touch Panel TP 610LC
Display
Display size (diagonal) 10 "
Display size (width) 203 mm
Display size (height) 152 mm
Resolution 768 x 1024 / 1024 x 768
Aspect ratio 4:3
Type of display TFT color (64K colors)
MTBF Backlights (25°C) 50000 h
System properties
Processor Cortex-A8 1000 MHz
VIPA HMI Touch Panel Hardware description
Technical data > 62K-NHC0-DH
HB160 | TP-ECO | 62K-NHC0 | GB | 14-27 19