Issue February 2002
Document Number: 13124
- 26 -
6.3.12. Parameter -12- : Locking of keyboard operation
The parameters of the main menu, e.g.: target power factor, switching time, etc. and the manual
operating mode MAN, can be protected against unauthorized adjustment by locking the keyboard.
Locking is activated, when the display indicates
≡
LO[ .
Keyboard operation Display
not locked
NO
locked
YES
If RST is selected (see page 20), NO is reset.
6.3.13. Parameter -13- : Functioning of the alarm relay
During normal and trouble-free operation, the alarm relay is operative. The contact is open. In case of
faults and of a breakdown of the supply voltage, the contact closes. The fault situation to which the
alarm relay shall react can be selected by means of parameter 13.
Alarm signals
≡
T
≡
HAR
≡
IEF
≡
[
≡
U
≡
0
≡
I
Display
X
0
X
1
X
2
X
3
X
4
X
5
X
6
XXX
7
XX
8
XX X
9
XX X X
10
XXXXXXX
11
X = Alarm relay reacts to this fault situation.
The different types of fault are described in the survey matrix under item 7.
If RST is selected (see page 20), 0 is reset.
6.3.14. Parameter -14- : Switching out the capacitor steps in case of alarm
Capacitor steps can be switched out when certain alarm signals are given. The fault alarm which shall
cause a switch-out can be selected by means of parameter 14. The specific kind of fault alarm
determines the switch-out behavior. The numbers 1- 3 indicate the priorities.
1 = the capacitor steps will be switched out immediately without time delay.
2 = the capacitor steps will be switched out after a time delay which can be modified (parameter 19)
3 = steps will continue being switched out until the fault alarm has disappeared.