Issue February 2002
Document Number: 13124
- 35 -
9. Flow Diagram: Parameters in the setting menu
-1- Modes of initialization
AU1 AU2 AU3
-2-
Type of measuring
voltage
L-0 or L-L
-3- Connection of measuring voltage
(Setting value as a function of the C.T. phase)
Connection of
measuring voltage
Connection of
measuring voltage
L1 – N L1 – N
... ...
L1 - L3 L1 - L3
-4- Type of switching program
1:1:1:1:1
...
1:2:4:8:8
-5- C/k value
-6- Number of switching steps
-7- Re-switching blocking delay
time
Display
20 sec
20
60 sec
60
180 sec
180
300 sec
300
-8- Switching-in delay time
LOAD or fixed time presetting is 2 to 500 seconds
(OFF: carried out according to the setting in the main menu)
-9- Switching-out delay time
LOAD or fixed time presetting is 2 to 500 seconds
(OFF: carried out according to the setting in the main menu)
-10- Switching in circular or series mode
Switching sequence Display
circular switching
[]
series switching
--
-11- Fixed steps (only in circular mode)