5. 1 Parameters related to switchover function setting
Item Setting range Description
Default value
Compression
voltage setting
[low voltage]
Operation
setting
Enable / Disable
Sets automatic switchover when the low
voltage occurs. (Enable : Switchover,
Disable : No switchover)
Enable
Pick Up 150.0 ~ 210.0 [V]
Low voltage setting
176 [V]
Time Delay 0.0 ~ 99.9 [S]
Sets the time of keeping the low voltage.
(Performing switchover if the low voltage is
kept for the specified period of time.)
1 [S]
Compression
voltage setting
[Over voltage]
Operation
setting
Enable / Disable
Sets automatic switchover when the
overvoltage occurs. (Enable : Switchover,
Disable : No switchover)
Enable
Pick Up 230.0 ~ 245.0 [V]
Overvoltage setting
242 [V]
Time Delay 0.0 ~ 99.9 [S]
Sets the time of keeping the overvoltage.
(Performing switchover if the low voltage is
kept for the specified period of time.)
1 [S]
Switching
frequency setting
[the low frequency]
Operation
setting
Enable / Disable
Sets automatic switchover when the low
frequency occurs. (Enable : Switchover,
Disable : No switchover)
Enable
Pick Up 58.0 ~ 60.0 [Hz]
Low frequency setting
59 [Hz]
Time Delay 0.0 ~ 99.9 [S]
Sets the time of keeping the low frequency.
(Performing switchover if the low voltage is
kept for the specified period of time.)
1 [S]
Switching
frequency setting
[the over frequency]
Operation
setting
Enable / Disable
Sets automatic switchover when the over-
frequency occurs. (Enable : Switchover,
Disable : No switchover)
Enable
Pick Up 60.0 ~ 62.0 [Hz]
Over-frequency setting
61 [Hz]
Time Delay 0.0 ~ 99.9 [S]
Sets the time of keeping the over-frequency.
(Performing switchover if the low voltage is
kept for the specified period of time.)
1 [S]
Normal voltage
range setting
Maximum
voltage
231.0 ~ 240.0 [V] Sets the maximum normal voltage value. 235 [V]
Minimum
voltage
150.0 ~ 215.0 [V] Sets the minimum normal voltage value. 181 [V]
Normal frequency
range setting
Maximum
frequency
60.0 ~ 62.0 [Hz]
Sets the maximum normal frequency value.
60.5 [Hz]
Minimum
frequency
58.0 ~ 60.0 [Hz]
Sets the minimum normal frequency value.
59.5 [Hz]
VITAC 200 provides the following parameters to reflect the power characteristics of the product
installation site and control the ATS smoothly.
5. Major parameters