5.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
ƽ Pressure in the system rises.
ƽ Operating current rises.
ƽ Cooling or heating efficiency drops.
ƽ Moisture in the refrigerant circuit may freeze and block capillary tubing.
ƽ Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and
evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come
out, the pipes have leakage.
1. Air purging with vacuum pump
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
Vacuu
pump
Vacuum
Va
cu
u
pump
Lo
Hi
Handle Hi
Two
-
way valve
Close
Manifold valve
Compound meter
Pressure
Pressu
gauge
-0.1Mpa
Handle Lo
Charge hose
Handle
Hi
Charge hose
(Outdoor unit)
Close
Three
-
way valve