7.4.3.5 High evaporator coil temp.T2 protection:
Compressor off
Compressor and
outdoor fan on
Outdoor motor off
For MS11D-07HRN1-QC2(2T0032100278),
Compressor off
Outdoor fan motor off
Compressor and outdoor
fan motor on
Compressor and outdoor
fan motor off
7.4.4 Auto-mode
The machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
T1-Ts
Cooling
Heating*
Fan only
Heating*: For cooling only models, they will run at fan speed
AC will run in auto mode in the below cases:
˄1˅ Press the forced auto button.
˄2˅ If AC is off, it will run in auto mode when timer on function is active.
˄3˅ After setting the mode, AC will run in auto mode if the compressor keeps not running for certain
time.