27
T1
Off
On
7.4.3.2 Outdoor fan running rules:
The outdoor units have single fan speed. The outdoor fan will run following the compressor except when
AC is in evaporator high temp. protection in heating mode , condenser high temp. protection in cooling
mode ,defrosting mode and the current protection.
7.4.3.3 Indoor fan running rules:
Auto fan action:
T1-TS
Low
Medium
The indoor fan speed will adjust according to the value of T1-T
S
.
7.4.3.4 Defrosting mode
˖
AC will enter the defrosting mode according to the value of temp difference between T2 and T1, and also
the compressor running time.
During the defrosting mode, the compressor keep running, indoor and outdoor motor will stop, defrost
lamp of the indoor unit will be lighted . Will be displayed.