WIRING CABLES AND DISTANCES
Wiring is recommended to be done using a cable copper conductors
PVC PVC
with
with insulation and jacket
(1)
(2) (3).
2
1
3
Electromagnetic lock VIZIT
Circuit
Wire
Maximum length, m
Diameter, mm
Cross-section, mm
2
0 2.0 5.
0 5.
0 8.
Power supply unit « Control Unit Reader«
Power supply unit Button for exit Electromagnetic lock««VIZITControl Unit «
50*
25
50*
50
* R C U shall
for a
Capacity of the cable connecting the eader to ontrol nit not exceed 3000 pF
(approx. 50 meters 2-wire cable).
2
Control Unit KTM600M
5
2
Reader RD-4F
EXIT 300M
button
Notes. EXIT 300M1. button is intended for lock release from inside of the building.
2. Recommended for use: power supply unit BPD18/12-1-1 orPower supply unit
19w/14.4v/EU(12V/1.5A).
is not supplied.
Electromechanical
lock / strike
2
4
2
Power supply unit
(1)
(2)
2
Control Unit KTM600M
Reader RD-4F
4
2
Power supply unit
Cross-sections of wires, and maximal distances are given in the table below:
VIZIT-KTM600F with Electromagnetic lock VIZIT
VIZIT-KTM600F with Electromechanical lock / strike
Wires cross-sections:
1. Power supply unit Control Unit Reader as shown in the above table.
2. Power supply unit Control Unit Electromechanical lock / strike wires cross-sections are selected with regard to:
operating voltage and current consumption parameters of the lock
output voltage of the power supply unit
distance between the power supply unit and lock
Therefore, consult qualified personnel about the lock, power supply unit and wires cross-sections.
««
««
-;
-;
-.
www. 5VIZIT-KTM600F Operating Instruction (revision 10)vizit-group.com 6 11/201 -