P11K P15K P18K P22K
High/Normal Load
1)
HO NO HO NO HO NO HO NO
Typical Shaft output hp [kW] 15 [11] 20 [15] 20 [15] 25 [18.5] 25 [18.5] 30 [22.0] 30 [22.0] 40 [30.0]
Enclosure IP20 B3 B3 B4 B4
Enclosure IP21 B1 B1 B2 B2
Enclosure IP55, IP66 B1 B1 B2 B2
Output current
Continuous (3x380–440 V) [A] 24 32 32 37.5 37.5 44 44 61
Intermittent (60 s overload) (3x380–440
V) [A]
38.4 35.2 51.2 41.3 60 48.4 70.4 67.1
Continuous (3x441–500 V) [A] 21 27 27 34 34 40 40 52
Intermittent (60 s overload)
(3x441–500 V) [A]
33.6 29.7 43.2 37.4 54.4 44 64 57.2
Continuous kVA (400 V AC) [kVA] 16.6 22.2 22.2 26 26 30.5 30.5 42.3
Continuous kVA (460 V AC) [kVA] 21.5 27.1 31.9 41.4
Max. input current
Continuous (3x380–440 V) [A] 22 29 29 34 34 40 40 55
Intermittent (60 s overload)
(3x380–440 V) [A]
35.2 31.9 46.4 37.4 54.4 44 64 60.5
Continuous (3x441–500 V) [A] 19 25 25 31 31 36 36 47
Intermittent (60 s overload)
(3x441–500 V) [A]
30.4 27.5 40 34.1 49.6 39.6 57.6 51.7
Additional specifications
IP21, IP55, IP66 max. cable cross-
section
5)
(line power, brake, load
sharing) [mm
2
(AWG)]
2)
16, 10, 16 (6, 8, 6) 16, 10, 16 (6, 8, 6) 35,-,-(2,-,-) 35,-,-(2,-,-)
IP21, IP55, IP66 max. cable cross-
section
5)
(motor) [mm
2
(AWG)]
2)
10, 10,- (8, 8,-) 10, 10,- (8, 8,-) 35, 25, 25 (2, 4, 4) 35, 25, 25 (2, 4, 4)
IP20 max. cable cross-section
5)
(line
power, brake, motor and load sharing)
10, 10,- (8, 8,-) 10, 10,- (8, 8,-) 35,-,-(2,-,-) 35,-,-(2,-,-)
Max. cable cross-section with
disconnect [AWG (mm
2
)]
2)
16, 10, 10 (6, 8, 8)
Estimated power loss
at rated max. load [W]
4)
291 392 379 465 444 525 547 739
Weight, enclosure IP20 (lbs [kg]) 26.46 [12] 26.46 [12] 51.81 [23.5] 51.81 [23.5]
Weight, enclosure IP21, IP55, 66 (lbs
[kg])
50.71 [23] 50.71 [23] 59.53 [27] 59.53 [27]
Efficiency
4)
0.98 0.98 0.98 0.98
Table 10.5 Line Power Supply 3x380–500 V AC (FC 302), 3x380–480 V AC (FC 301)
Specifications
VLT
®
AutomationDrive Instruction
Manual
MG33AM22 - VLT
®
is a registered Danfoss trademark 10-5
10
10

Table of Contents