Troubleshooting GP Repair
wc_tx000548gb.fm 82
6.11 No Voltage at Receptacles—Flowchart 1C
wc_gr003114
Checking main circuit breaker
Check voltage to main circuit breaker.
Check wiring
to generator
terminal strip.
Repair or replace
wiring as
needed.
Is
correct voltage
measured?
Ye s
No
No
Check outgoing voltage from main
circuit breaker.
Replace the main
circuit breaker.
Is
correct voltage
measured?
Ye s
Check continuity of wiring to receptacles.
Repair/replace
the wiring.
Replace
the receptacle.
Does
wiring have
continuity?
Ye s
No