90 Commissioning WAGO-I/O-SYSTEM 750
750-843 ETHERNET Controller 10 MBit
Manual
Version 1.2.0
Pos: 78.6 /Serie 750 (WAGO-I/O-SYST EM)/I n Betri eb neh men/Fel dbus knote n in Betr ieb ne hmen/ PC und Fel dbus knot en ansc hließ en (Über schr ift 2) @ 4\ mod_1238677467406_21.docx @ 29815 @ 2 @ 1
8.1 Connecting Client PC and Fieldbus Nodes
Pos: 78.7 /Serie 750 (WAGO-I/O-SYST EM) /In Betr ieb ne hmen/ Feldb uskn oten in Be trie b nehmen/ PC und F eldb uskn oten an Fel dbusa nschl uss an schli eßen ( Aufzähl ung An fang) @ 7\mod_1270715583038_21.docx @ 54969 @ @ 1
1. Use the fieldbus cable to connect the fieldbus connection of your
mechanically and electrically assembled fieldbus node to an open interface
on your computer.
The client PC must be equipped with a network card for this connection.
The controller transfer rate then depends on the network card of your client
PC.
Pos: 78.8 /Serie 750 (WAGO-I/O-SYST EM )/I n Be tri eb neh men/ Fel dbus kn oten i n Betr ieb neh men/H oc hla uf u nd L EDs (C ontr oll er) @ 4\ mod_1243521648173_21.docx @ 34301 @ @ 1
After the power is switched on, the controller is initialized. The fieldbus controller
determines the I/O module configuration and creates a process image. During
startup, the I/O LED (red) will flash. After a brief period, the I/O LED lights up
green, indicating that the fieldbus controller is operational.
Pos: 78.9 /Serie 750 (WAGO-I/O-SYST EM)/ In Betr ieb ne hmen/ Feldb uskn oten in Be trieb ne hmen/H oc hlauf und LEDs - Fehler 6-4: no ch kei ne IP-A dresse z ugewi esen @ 4\mod_1243590721843_21.docx @ 34504 @ @ 1
If an error has occurred during startup, a fault code is flashed by the I/O LED.
If the I/O LED flashes 6 times (indicating error code 6) and then 4 times
(indicating error argument 4), an IP address has not been assigned yet.