Ungrounded Delta or Wye Load 3-phase, 2-leg DIN-A-MITE
NOTE: The current transformers must be in the controlled legs on a 2-leg DIN-A-MITE. The
load wires must pass through the current transformers in the same direction.
Non-latching Alarm Option
(models DC_ _ -
_ _ S _ - H _ _ _ )
Open Heater and Shorted SCR Alarm
The shorted SCR detector compares the input
command signal and actual load current. If
load current is present without an input signal
then the shorted SCR alarm will energize a
triac (on board the DIN-A-MITE) output.
An open-heater or partial open-heater state is
detected when a command signal is present
and a reduced or no output current is detected.
The alarm output is then energized.
This is a non-latching alarm. This output can
be used to drive various indication devices,
such as a coil, light, buzzer, etc. See the
alternative latching circuit section below.