Benchmark Platinum-Edge: Operation-Service Manual
SECTION 4 INITIAL START-UP
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 41 of 146
NATURAL GAS Manual Combustion Calibration Instructions
BMK 2000 Dual Fuel Units
70%
6.5% ± 0.2%
≤20 ppm
<100 ppm
50%
6.5% ± 0.2%
≤20 ppm
<100 ppm
40%
6.5% ± 0.2%
≤20 ppm
<50 ppm
30%
6.5% ± 0.2%
≤20 ppm
<50 ppm
16%
5.5% ± 0.2%
≤20 ppm
<50 ppm
TABLE 4-3d: NATURAL GAS Final Valve Positions: BMK 2500 & 3000
BMK 2500
Single Fuel Dual Fuel
NO
x
CO
Valve %
O
2
%
Valve %
O
2
%
70%
5.9% ± 0.2%
70%
5.9% ± 0.2%
≤20 ppm
<100 ppm
50%
6.0% ± 0.2%
45%
6.2% ± 0.2%
≤20 ppm
<100 ppm
40%
6.3% ± 0.2%
30%
6.0% ± 0.2%
≤20 ppm
<50 ppm
30%
6.3% ± 0.2%
20%
5.8% ± 0.2%
≤20 ppm
<50 ppm
16%
6.0% ± 0.2%
16%
6.0% ± 0.2%
≤20 ppm
<50 ppm
BMK 3000
70%
5.1% ± 0.2%
85%
5.4% ± 0.2%
≤20 ppm
<100 ppm
50%
6.1% ± 0.2%
65%
5.5% ± 0.2%
≤20 ppm
<100 ppm
40%
5.0% ± 0.2%
45%
5.7% ± 0.2%
≤20 ppm
<50 ppm
30%
6.4% ± 0.2%
30%
5.6% ± 0.2%
≤20 ppm
<50 ppm
14%
6.4% ± 0.2%
14%
6.2% ± 0.2%
≤20 ppm
<50 ppm
TABLE 4-3e: NATURAL GAS Final Valve Positions: BMK 5000, Single & DF
Valve Position
Standard NO
x
Ultra-Low NO
x
CO
Single
Fuel
Dual
Fuel
O
2
% NO
x
O
2
% NO
x
70%
5.5% ± 0.5%
<20 ppm
6.0% ± 1.0% ≤9 ppm
<100 ppm
50%
5.5% ± 0.5%
<20 ppm
6.0% ± 1.0% ≤9 ppm
<100 ppm
40% 5.5% ± 0.5%
<20 ppm
6.0% ± 1.0% ≤9 ppm
<50 ppm
30% 5.5% ± 0.5%
<20 ppm
6.0% ± 1.0% ≤9 ppm
<50 ppm
18%
6.0% ± 1.0%
<20 ppm
6.5% ± 1.5% ≤9 ppm
<50 ppm
TABLE 4-3e: NATURAL GAS Final Valve Positions: BMK 6000, Single & DF
Valve Position
Standard NO
x
Ultra-Low NO
x
CO
Single
Fuel
Dual
Fuel
O
2
% NO
x
O
2
% NO
x
70% 85%
5.5% ± 0.5%
<20 ppm
6.0% ± 1.0% ≤9 ppm
<100 ppm
50% 65%
5.5% ± 0.5%
<20 ppm
6.0% ± 1.0% ≤9 ppm
<100 ppm
40% 45%
5.5% ± 0.5%
<20 ppm
6.0% ± 1.0% ≤9 ppm
<50 ppm

Table of Contents

Other manuals for Watts Aerco Benchmark Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts Aerco Benchmark Series and is the answer not in the manual?

Watts Aerco Benchmark Series Specifications

General IconGeneral
BrandWatts
ModelAerco Benchmark Series
CategoryBoiler
LanguageEnglish

Related product manuals