0
Quick Reference of Parameters, Alarms and Faults
CFW500 | 0-1
QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS
Parameter Description
Adjustable
Range
Factory
Setting
User
Setting
Properties Groups Page
P0000 Access to Parameters 0 to 9999 0 5-2
P0001 Speed Reference 0 to 65535 ro READ 16-1
P0002 Output Speed (Motor) 0 to 65535 ro READ 16-1
P0003 Motor Current 0.0 to 200.0 A ro READ 16-1
P0004 DC Link Voltage (Ud) 0 to 2000 V ro READ 16-1
P0005 Output Frequency (Motor) 0.0 to 500.0 Hz ro READ 16-2
P0006 Inverter Status 0 = Ready
1 = Run
2 = Undervoltage
3 = Fault
4 = Self-Tuning
5 = Configuration
6 = DC-Braking
7 = Sleep Mode
ro READ 16-2
P0007 Output Voltage 0 to 2000 V ro READ 16-3
P0009 Motor Torque -1000.0 to 1000.0 % ro, V V W READ 16-4
P0010 Output Power 0.0 to 6553.5 kW ro READ 16-4
P0 011 Power Factor -1.00 to 1.00 ro READ 16-4
P0012 DI8 to DI1 Status Bit 0 = DI1
Bit 1 = DI2
Bit 2 = DI3
Bit 3 = DI4
Bit 4 = DI5
Bit 5 = DI6
Bit 6 = DI7
Bit 7 = DI8
ro READ, I/O 12-15
P0013 DO5 to DO1 Status Bit 0 = DO1
Bit 1 = DO2
Bit 2 = DO3
Bit 3 = DO4
Bit 4 = DO5
ro READ, I/O 12-23
P0014 AO1 Value 0.0 to 100.0 % ro READ, I/O 12-6
P0015 AO2 Value 0.0 to 100.0 % ro READ, I/O 12-6
P0016 FO Value in % 0.0 to 100.0 % ro READ, I/O 12-12
P0017 FO Value in Hz 0 to 20000 Hz ro READ, I/O 12-12
P0018 AI1 Value -100.0 to 100.0 % ro READ, I/O 12-1
P0019 AI2 Value -100.0 to 100.0 % ro READ, I/O 12-1
P0020 AI3 Value -100.0 to 100.0 % ro READ, I/O 12-1
P0021 FI Value in % -100.0 to 100.0 % ro READ, I/O 12-9
P0022 FI Value in Hz 0 to 20000 Hz ro READ, I/O 12-10
P0023 Main SW Version 0.00 to 655.35 ro READ 6-1
P0024 Secondary SW Version 0.00 to 655.35 ro READ 6-1
P0027 Plug-in Module Configuration 0 = Without Plug-in
1 = CFW500-IOS
2 = CFW500-IOD
3 = CFW500-IOAD
4 = CFW500-IOR
5 = CFW500-CUSB
6 = CFW500-CCAN
7 = CFW500-CRS232
8 = CFW500-CPDP
9 = CFW500-CRS485
11 = CFW500-CETH-IP
CFW500-CEMB-TCP
CFW500-CEPN-IO
ro READ 6-1