SSW-06 - QUICK PARAMETER REFERENCE
QUICK PARAMETER REFERENCE, FAULT AND STATUS MESSAGES
Software:V1.3X
Application:
Model:
Serial Number:
Person Responsible:
Date: / / .
I. Parameters
Parameter Description Adjustable Range
Factory
Unit
User´s
Page
Setting Setting
P000 Access Parameter 0 to 999 0 - 77
READ ONLY PARAMETERS P001 to P099
P001 Soft-Starter Current 0 to 999.9 - % 78
(%In of the Soft-Starter)
P002 Motor Current (%In of the Motor) 0 to 999.9 - % 78
P003 Motor Current 0 to 9999.9 - A 78
P004 Power Supply Voltage 0 to 999 - V 78
P005 Network Frequency 0 to 99.9 - Hz 78
P006 Soft-Starter Status 0=rdy - ready - - 78
1=Sub - Sub
2=Exx - Error
3=ruP - Run Up
4=FuLL - Full Volt.
5=PASS - By-pass
6=ECO - Reserved
7=rdo - Run Down
8=br - Braking
9=rE - FWD/REV
10=JOG - JOG
11=dly - Delay P630
12=G.di - Gen. Disable
P007 Output Voltage 0 to 999 - V 79
P008 Power Factor 0 to 1.00 - - 79
P009 Motor Torque (% Tn of the Motor) 0 to 999.9 - % 79
P010 Output Power 0 to 6553.5 - kW 79
P011 Apparent Output Power 0 to 6553.5 - kVA 79
P012 Digital Input Status Dl1 to Dl6 0 = Inactive - - 80
1 = Active
P013 Status RL1, RL2 and RL3 0 = Inactive - - 80
1 = Active
P014 Last Fault 03 to 77 - - 81
P015 Second Previous Fault 03 to 77 - - 81
P016 Third Previous Fault 03 to 77 - - 81
P017 Fourth Previous Fault 03 to 77 - - 81
P023 Software Version X.XX - - 81
P030 Current of Phase R 0 to 9999.9 - A 81
P031 Current of Phase S 0 to 9999.9 - A 81
P032 Current of Phase T 0 to 9999.9 - A 81
P033 R-S Line Voltage 0 to 999 - V 81
P034 S-T Line Voltage 0 to 999 - V 81
P035 T-R Line Voltage 0 to 999 - V 81