The insulation resistance shall be measured using a Megohmmeter. The test voltage
for the motors winding shall be according the table below in accordance with the
standard IEEE43
Winding rated voltage (V)
Insulation resistance test
direct voltage (V)
These measurements shall be made before connecting the supply cables.
A possible diagram to measure the insulation resistance for complete winding is
showed below. The measure must be taken 1 minute after apply the DC voltage with
the insulation tester.
According to standard IEEE 43 the recommended minimum insulation resistance
values at 40ºC in MΩ are the following:
5 MΩ, for low voltage motors (U < 1,1kV)
100 MΩ, for medium voltage motors (1,1kV < U < 11kV)
Insulation resistance depends mainly from the winding temperature as showed in the
following table: