22
Standard parameter setup codes, descriptions, range of values, and default values
Parameter description
(menu)
1
Temperature Units
(Advanced only)
(Basic, Advanced, and
100ºC)
Relay On Temperature
(Basic and Advanced)
-40ºF to 212ºF (-40ºC to
100ºC)
Anti-Short Cycle Delay
(Basic and Advanced)
Temperature Setback
(Advanced only)
-50ºF to 50ºF (-30ºC to
30ºC)
Sensor Offset Adjustment
(Advanced only)
-5ºF to 5ºF (-3ºC to 3ºC)
High Temperature Stop
(Advanced only)
-40ºF to 212ºF (-40ºC to
100ºC)
Low Temperature Stop
(Advanced only)
-40ºF to 212ºF (-40ºC to
100ºC)
(Basic and Advanced)
deenergized
1 = output relay energized
Level Adjustment
0 to 10; 0 = backlight off,
10 = brightest backlight
Defrost Cycle Time
(Advanced only)
Defrost Interval
(Advanced only)
Start or Stop Defrost Off-
Cycle (Advanced only)
new Defrost Cycle Change
1 to 0 to Stop a Defrost
(Advanced only)
Mode 1 = Start Defrost
1 The default values for general application A421 models are shown. OEM A421 models may have different default values.
A421 Control parameter setup menus
• The A421 Temperature Controls have a Basic and an Advanced setup menu. You can scroll through the parameter
setup codes, view and edit parameter values, and set up your control for your application requirement. The control
also has a Restricted adjustment menu. See Restricting user adjustment for more information.
Note: The A421 Control retains a copy of the saved parameter values in memory. When you change and save a new value, the
new value immediately overwrites the previous value and saves to memory. In the event of a power failure, brown out, or
when you disconnect power from the control, all of the current parameter values in memory are retained. Reconnecting power
to the control restores all of the saved values.