34
Section 7
Troubleshooting
Evaporator Troubleshooting
Replace fuse(s). Check for short circuits or
overload conditions.
Defective timer or defrost thermostat
Replace defective component.
Wait for completion of cycle.
Walk-in temperature too high.
Adjust thermal expansion valve.
System low on refrigerant
Locate and repair leak, recover, evacuate
and recharge.
Manually defrost coil. Check defrost
controls.
Ice accumulating on ceiling around
evaporator and/or on fan guards,
venturi, or blades.
Defrost duration is too long
Adjust defrost termination thermostat (if
adjustable).
Fan delay not delaying fans after defrost
period
Replace defective defrost thermostat.
Defective defrost thermostat or timer
Replace defective component.
Too many defrost cycles per day
Reduce number of defrost cycles per day.
Frost on coil after defrost cycle.
Coil temperature not getting above
freezing point during defrost
Not enough defrost cycles per day
Adjust timer for more defrost cycles per
day
Adjust timer for longer cycle, check
defrost thermostat mounting
Defective timer or defrost thermostat
Replace defective component.
Ice accumulating in drain pan.
Unit not pitched properly
Defective drain line heater
Defective timer or thermostat
Replace defective component.