23
▼ Control parameters interface
Press continuously and the inverse cursor will enter into the control
parameters interface. Press or to modify the following control
parameters.
Parameter Set
Over Volt. Disc : 16.0V
Charg Lmt : 15.5V
Over Volt. Rect : 15.0V
ENTER/
→
↑/ +
↓/ -
Parameter Set
Equal Chrg : 14.6V
Boost Chrg : 14.4V
Float Chrg : 13.8V
Parameter Set
Boost V. Rect : 13.2V
Low V. Rect : 12.6V
Under V. Rect : 12.2V
Parameter Set
Under V. Warn : 12.0V
Low V. Disc : 11.1V
Discharg Lmt : 10.8V
If battery type is GEL,
the parameters cannot be
modified.