Westinghouse iPro4200 - Troubleshooting Guide; Common Generator Problems and Solutions

Westinghouse iPro4200
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Westinghouse Portable Power | 23
WARNING
Before attempting to service or troubleshoot the generator, the owner or service technician must rst read the owner’s
manual and understand and follow all safety instructions. Failure to follow all instructions may result in conditions that
can lead to voiding of the EPA certication or product warranty, serious personal injury, property damage or even death.
TROUBLESHOOTING
PROBLEM POTENTIAL CAUSE SOLUTION
Engine is running, but no
electrical output.
1. Reset breaker is tripped. 1. Reset the reset breaker (see page 15).
2. The power cord’s plug connector is not fully
engaged in the inverter’s outlet.
2. Verify plug connector is rmly engaged
in the inverter’s outlet.
3. Faulty or defective power cord. 3. Replace power cord.
4. Faulty or defective electrical appliance. 4. Try connecting a known good appliance
to verify the inverter is producing electrical
power.
5. GFCI outlet is tripped. 5. Press the reset button on the GFCI
outlet (see page 22).
6. If trying 1-5 above does not solve the
problem, the cause might be the inverter has
a fault.
6. Take the generator to your nearest
authorized service dealer.
Engine will not start or remain
running while trying to start.
1. Inverter is out of gasoline. 1. Add gasoline to the inverter (see page 13).
2. Fuel ow is obstructed or fuel shuto valve
is in the OFF position.
2. Inspect and clean fuel delivery passages
and make sure fuel shut o is ON.
3. Dirty air lter. 3. Check and clean the air lter (see page 18).
4. Low oil level shutdown switch is preventing
the unit from starting.
4. Check oil level and add oil if necessary
(see page 17).
5. Spark plug boot is not fully engaged with
the spark plug tip.
5. Firmly push down on the spark plug boot
to ensure the boot is fully engaged.
6. Spark plug is faulty. 6. Remove and check the spark plug.
Replace if faulty (see page 20).
7. Dirty/plugged spark arrestor. 7. Check and clean the spark arrestor (see
page 21).
8. Stale fuel. 8. Drain fuel and replace with fresh fuel.
Inverter suddenly
stops running.
1. Inverter is out of fuel. 1. Check fuel level (see page 14). Add fuel
if necessary.
2. The low oil shut down switch has stopped
the engine.
2. Check oil level and add oil if necessary
(see page 17).
3. Too much load. 3. Restart the inverter and reduce the load.
Engine runs
erratic; does not hold a
steady RPM.
1. Choke was left in the CHOKE position. 1. Move choke to the RUN position.
2. Dirty air lter. 2. Clean the air lter (see page 18).
3. Applied loads maybe cycling on and o. 3. As applied loads cycle, changes in
engine speed may occur; this is a normal
condition.