This thermostat is intended for use with a low voltage NEC
Class II system. Do not use this thermostat with a line voltage
system. If in doubt about whether your wiring is millivolt, line,
or low voltage, have it inspected by a qualifi ed heating and air
conditioning contractor or electrician.
Do not exceed the specifi cation ratings.
All wiring must conform to local and national electrical codes
and ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could
cause the control to malfunction.
Blue 2” Single Stage Thermostat
Installation and Operating Instructions
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.
APPLICATIONS
For use with the following Class II systems:
• Single Stage systems
Single-stage heat pump systems with no Aux heat
DO NOT USE WITH:
Systems exceeding 30 VAC and 1.5 amps
3-wire zoned hydronic heating systems
1F80-0224 Thermostat
Model Programming Choices
1F80-0224
24-hour Programmable
SPECIFICATIONS
Electrical Rating:
Battery Power ................................................. mV to 30 VAC, 50/60 Hz or DC
Input-Hardwire ................................................ 20 to 30 VAC
Terminal Load ........................................................ 1.0 A per terminal, 1.5A maximum all terminals combined
Setpoint Range ...................................................... 45° to 90°F (7° to 32°C)
Differential (Single Stage) ...................................... Heat 0.6°F; Cool 1.2°F (adjustable)
Differential (Heat Pump) ........................................ Heat 1.2°F; Cool 1.2°F (adjustable)
Operating Ambient ................................................. 32° to +105°F (0° to +41°C)
Operating Humidity ................................................ 90% non-condensing max.
Shipping Temperature Range ................................ -40° to +150°F (-40° to +65°C)
Dimensions Thermostat ......................................... 3-3/4”H x 4-3/4”W x 1-1/2”D
PRECAUTIONS
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
CAUTION
!
Do not use on circuits exceeding specifi ed voltage.
Higher voltage will damage control and could cause
shock or fi re hazard.
Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will damage
thermostat and could cause personal injury and/or
property damage.
Thermostat installation and all components of the
system shall conform to Class II (current limited)
circuits per the NEC code. Failure to do so could cause
a fi re hazard.
WARNING
!
www.white-rodgers.com
PART NO. 37-7014B
Replaces 37-7014A
0924

Questions and Answers

  • M
    Matthew BurkeAug 15, 2025
    How to fix a White Rodgers 1F80-0224 Thermostat that is not heating?
    • M
      Michael BrownAug 15, 2025
      If your White Rodgers Thermostat is not producing heat, consider these potential solutions: * **System Switch:** Ensure the System Switch is set to Heat and the setpoint is higher than the room temperature. * **Connections:** Verify that the thermostat and system wires are securely attached. * **System Service:** If the thermostat doesn't click after being reset, contact a heating and cooling service person or the place of purchase for a replacement.
  • D
    David MooreAug 18, 2025
    How to calibrate temperature on White Rodgers 1F80-0224?
    • T
      Tiffany HallAug 18, 2025
      If the thermostat setting and thermometer reading on your White Rodgers Thermostat disagree, the thermometer setting requires adjustment. You can adjust the thermometer +/- degrees as listed in item 8 of the Configuration Menu.
  • K
    Kristy SmithAug 21, 2025
    What to do if my White Rodgers 1F80-0224 is not cooling?
    • R
      Ricardo Baker MDAug 22, 2025
      If your White Rodgers Thermostat is not cooling, here are some things to check: * **System Switch:** Make sure the System Switch is set to Cool and the setpoint is lower than the room temperature. * **Connections:** Verify that the thermostat and system wires are securely attached. * **Cooling System:** If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating system is operating correctly.
  • S
    Stephen AvilaAug 25, 2025
    Why is my White Rodgers Thermostat not following the program?
    • D
      dawn87Aug 25, 2025
      If your White Rodgers Thermostat isn't following the set program, check these items: * **AM/PM Settings:** Verify the AM/PM settings in the program are correct. * **Clock AM/PM:** Ensure the AM/PM setting on the clock is accurate. * **Voltage Spike:** If a voltage spike or static discharge occurred, use the Reset Operation.
  • J
    Jennifer OchoaAug 27, 2025
    What to do if White Rodgers 1F80-0224 display is blank?
    • P
      Peter GrahamAug 27, 2025
      If your White Rodgers Thermostat has a blank display or the keypad isn't responding, it might be due to a voltage spike or static discharge. In this case, use the Reset Operation.
  • C
    Christian MillerAug 30, 2025
    Why does my White Rodgers 1F80-0224 clock lose time?
    • B
      Benjamin MitchellAug 30, 2025
      If your White Rodgers Thermostat clock loses or gains time, this could be due to a loss of power to the thermostat. Refer to the No Heat/No Cool/No Fan troubleshooting steps to check the system.
  • R
    roysmithSep 2, 2025
    How to troubleshoot no heat, no cool, or no fan on my White Rodgers Thermostat?
    • K
      Kelly AlvaradoSep 2, 2025
      If your White Rodgers Thermostat isn't producing heat, cool air, or running the fan, check the following: * **Blown fuse or tripped circuit breaker:** Replace the fuse or reset the breaker. * **Furnace power switch:** Ensure the furnace power switch is turned to the ON position. * **Furnace blower compartment door:** Make sure the door or panel is correctly placed to engage the safety interlock or door switch.
  • R
    rebecca00Sep 5, 2025
    Why does my White Rodgers Thermostat's heat, cool, or fan run constantly?
    • D
      Darryl TaylorSep 5, 2025
      If your White Rodgers Thermostat has the heat, cool, or fan running constantly, here's what to check: * **Wiring:** Inspect each wire connection to ensure they are not shorted or touching. * **Thermostat:** Try resetting the thermostat. * **Heat/Cool/Fan system:** If the system operates correctly after resetting, consider replacing the thermostat. * **Fan Switch:** Check if the Fan Switch is set to Fan On.
  • A
    amber23Sep 8, 2025
    Why does my White Rodgers 1F80-0224 Thermostat have short or long cycles?
    • A
      amber48Sep 8, 2025
      If your White Rodgers Thermostat's furnace or cooling cycles are too fast or slow, the cycle rate may be influenced by the thermostat's location or the size of the heating or cooling system. You can adjust the cycle rate using Item 3 (CR Heat) or Item 4 (CR Cool) in the Configuration Menu.
  • B
    Beth ArellanoSep 12, 2025
    Why does my White Rodgers 1F80-0224 start heating or cooling early?
    • R
      Ronald CurtisSep 12, 2025
      If the heat or cool starts early on your White Rodgers Thermostat, it could be due to the EMR being activated. Refer to Configuration Menu (Item 3).

Summary

APPLICATIONS

Usage Limitations

Details systems that should not be used with this thermostat.

PRECAUTIONS

INSTALLATION

Remove Old Thermostat

Step-by-step instructions for safely removing the previous thermostat.

Attach Thermostat Base to Wall

Guidance on mounting the new thermostat base securely.

Battery Location and Replacement

Details on battery installation, use, and replacement.

Wiring Diagrams

Illustrations of typical system wiring configurations.

INSTALLER;CONFIGURATION MENU

Configuration Menu Options

Details on settings like System Configuration, Cool Savings, and EMR.

OPERATION

PROGRAMMING

TROUBLESHOOTING

Symptom Analysis

Diagnosing common issues like no heat, no cool, or constant running.