21WIKA operating instructions pressure transmitter, model IS-3
MM/YYYY country code based on 14095850.02 12/2014 EN/CN
EN
3.Specications
Electrical connection 94/9/EC
(ATEX)
EPL Group Ambient and medium tem-
peratures (°C)
Temperature class /
surface temperature
Circular connector 7/8-16 UN (4-pin)
Not adjustable
IS-3-*-****-***-*******-*ZM6Z**-****
M1 Ma I -40 ≤ T
a
≤ +70 N/A
1/2G
3G
Ga/Gb
Gc
IIC -40 ≤ T
a
≤ +60
-40 ≤ T
a
≤ +70
-40 ≤ T
a
≤ +70
T6
T5
T4
1/2D Da/Db IIIC -40 ≤ T
a
≤ +40 (750 mW)
-40 ≤ T
a
≤ +70 (650 mW)
-40 ≤ T
a
≤ +70 (550 mW)
135 °C
Angular connector acc. to
DIN EN 175301-803 A
Adjustable
IS-3-*-****-***-*******-*TA3Z**-****
IS-3-*-****-***-*******-*TAWZ**-****
IS-3-*-****-***-*******-*TAVZ**-****
M1 Ma I -30 ≤ T
a
≤ +105 N/A
1/2G
3G
Ga/Gb
Gc
IIC -30 ≤ T
a
≤ +60
-30 ≤ T
a
≤ +75
-30 ≤ T
a
≤ +105
T6
T5
T4
1/2D Da/Db IIIC -30 ≤ T
a
≤ +40 (750 mW)
-30 ≤ T
a
≤ +70 (650 mW)
-30 ≤ T
a
≤ +100 (550 mW)
135 °C
Cable outlet IP 67
Adjustable
IS-3-*-****-***-*******-*TDPA**-****
M1 Ma I -30 ≤ T
a
≤ +70 N/A
1/2G
3G
Ga/Gb
Gc
IIC -30 ≤ T
a
≤ +60
-30 ≤ T
a
≤ +70
-30 ≤ T
a
≤ +70
T6
T5
T4
1/2D Da/Db IIIC -30 ≤ T
a
≤ +40 (750 mW)
-30 ≤ T
a
≤ +70 (650 mW)
-30 ≤ T
a
≤ +70 (550 mW)
135 °C
Cable outlet IP 68
Cable gland
Not adjustable
IS-3-*-****-***-*******-*ZXPA**-****
Adjustable
IS-3-*-****-***-*******-*TXPA**-****
M1 Ma I -30 ≤ T
a
≤ +70 N/A
1G
1/2G
3G
Ga
Ga/Gb
Gc
IIC -30 ≤ T
a
≤ +60
-30 ≤ T
a
≤ +70
-30 ≤ T
a
≤ +70
T6
T5
T4
1D
1/2D
Da
Da/Db
IIIC -30 ≤ T
a
≤ +40 (750 mW)
-30 ≤ T
a
≤ +70 (650 mW)
-30 ≤ T
a
≤ +70 (550 mW)
135 °C
Cable outlet IP 68
Cable gland conduit ½ NPT
Not adjustable
IS-3-*-****-***-*******-*Z5WA**-****
M1 Ma I -30 ≤ T
a
≤ +70 N/A
1G
1/2G
3G
Ga
Ga/Gb
Gc
IIC -30 ≤ T
a
≤ +60
-30 ≤ T
a
≤ +70
-30 ≤ T
a
≤ +70
T6
T5
T4
1D
1/2D
Da
Da/Db
IIIC -30 ≤ T
a
≤ +40 (750 mW)
-30 ≤ T
a
≤ +70 (650 mW)
-30 ≤ T
a
≤ +70 (550 mW)
135 °C