14
P:4,3bar V:100%
> Automatic rw<
1 select
operational mode
1.01 mode
> automatic <
1.02 pump manu.
> OFF <
1.03 valve manu.
> OFF <
2 equipment
configuration
2.01 WILO RCE
Vx.xx dd.mm.yyyy
2.02 language
> English <
2.03 sensor typ
> 5,00 m <
2.04 tank form
> verti.cylin. <
2.05 tank height
> 199 cm <
2.06 h sensor
> 025 cm <
2.07 h overflow
> 091 cm <
Table 1: Menu structure (Attention: observe notes under point 4)
Menu point Description
Standard display:
P: Current system pressure on pressure side
V: Cistern filling volume
RW: Rainwater from cistern
DW: Drinking water from backfeed tank
Selection of unit operating mode
(see chapter 4.1)
Manual function for pump. Switches on pump for
as long as key is pressed (F or G)
Only in Manual operating mode (menu 1.01)
Manual function for valve. Opens valve for as
long as key is pressed
Only in Manual operating mode (menu 1.01)
Displays unit’s software version Vx.xx
and date of issue dd.mm.yyyy.
Selection of menu language
Selection of level sensor used
H
max
corresponds to the upper limit (2 or 5 mWS)
of the measuring range
Selection of available tank form
Specification of tank height
Installation height of sensor above tank bottom.
Absolute value measured in relation to tank
bottom.
Installation height of overflow above tank bottom
Absolute value measured in relation to tank
bottom.
Automatic
OFF
manual
drinkwater
ON
OFF
ON
OFF
Deutsch
English
Nederlands
Francais
> 2.00 m <
> 5.00 m <
base x heigth
horizontal cylinder
vertical cylinder
spherical
00 – H
max
[cm]
00 – H
max
[cm]
(but less than
2.05)
00 – H
max
[cm]
but greater than
2.06 and less 2.05
Deutsch
5.00 m
vertical cylinder
199 cm
025 cm
091 cm
Automatic
OFF
OFF
Setting range Factory setting