3.4.3. Switchgear
Mainsconnection: 1~230Vor3~400V
Frequency: 50/60Hz
Max.current: 12 A per pump
Powerconsumption:
Contactortaut:15VA
Downtimestatus:8VA
Max.switchingcapacityP
2
: 4kW,AC3perpump
Max.fuseprotectionon
mainsside:
25A,slow-blow(16A*,
slow-blow)
Activationtype: Direct start-up
Ambient/operating temper-
ature:
-30to+60°C
Storagetemperature: -30to+60°C
Max.relativehumidity: 50%
Protectionclass: IP 54
Controlvoltage: 24 VDC
Alarm contact switching
capacity:
max.250V~,1A
Housingmaterial: Polycarbonate, UV-resistant
Housingdimensions(Wx-
HxD):
289x239x107mm
Electricalsafety: Degree of contamination II
*"S"versionwithshock-proof/CEE16plug
3.5. Type key
Example: Wilo-Control MS-L 2x4kW-M-DOL-S
MS
MicroControlswitchgearforxedspeedpumps
L
Level-dependent control of the pump
2x
Max.numberofpumpsthatcanbeconnected
4kW
Max.permissibleratedpower(P
2
) per pump
M
Mainsconnection:
None=Choiceof1~230Vor3~400V
M=alternatingcurrent(1~230V)
T4=three-phasecurrent(3~400V)
DOL
direct-on-line starting of pumps
S
Versionofswitchgear:
Without = standard version with main switch
S = Version for lifting units without main switch,
with cable and plug
O = Version without main switch and without
plug
3.6. Options
Byinsertingarechargeablebattery(available
as an accessory) alarm signals can be emitted
independent of the electricity network in case of
afault.Anaudibleconstanttonewillbeemitted
as an alarm.
3.7. Scope of delivery
Standard variant and "O" variant
• Switchgear
• 2xreducingsealsforthreadedcableconnection
• 2xassembledjumperwiresformainsconnection
• Installation and operating instructions
Variant "S"
• Switchgearwithconnectedcableandplug:
• 1~230V:Shockproofplug
• 3~400V:CEEphaseinverterplugwithphase
inverter
• Installation and operating instructions
3.8. Accessories
• Float switch for wastewater and sewage free of
faeces
• Float switch for abrasive sewage containing
faeces
• NiMHrechargeablebattery(9V/200mAh)for
alarmsignalstoindicateapowerfailure
• Horn230V,50Hz
• Flashlight230V,50Hz
• Signallamp230V,50Hz
Accessories have to be ordered separately.
4. Transport and storage
4.1. Delivery
On delivery, check immediately that the ship-
mentiscompleteandundamaged.Ifanyparts
are damaged or missing, the transport company
orthemanufacturermustbenotiedontheday
of delivery. Claims made after this date cannot be
recognised. Damage to parts must be noted on
the freight documentation.
4.2. Transport
Only the packaging used by the manufacturer or
supplier may be used for transport. This normally
precludes the possibility of damage occurring
duringtransportandstorage.Thepackaging
shouldbestoredinasafeplaceforreuseifthe
product is frequently used at different locations.
4.3. Storage
On delivery, switchgears may be placed into tem-
porary storage for up to 1 year until use providing
the details below are observed.
The following should be taken into consideration
forstorage:
• Placethepackagedswitchgearonarmsubsur-
face.
• Theswitchgearsmaybestoredfrom-30°Cto
+60°Catamax.relativeairhumidityof50%.
Thestoreroommustbedry.Werecommend
afrost-protectedroomforstoragewithatem-
peraturebetween10°Cand25°Candarelative
airhumidityof40%to50%.
Avoid formation of condensate!
• Seal the threaded cable connections securely to
prevent ingress of moisture.
• Connected power supply cables and attached
plugs should be protected from kinking, damage,
and moisture.