EasyManua.ls Logo

Wilo Control MS-L 2x4kW Series - Mounting and Electrical Connection Basics

Wilo Control MS-L  2x4kW Series
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InstallationandoperatinginstructionsWilo-ControlMS-L2x4kW 33
INSTALLATION English
4. Fixtheswitchgearusingfourscrews(max.Ø:
4mm)andappropriateanchorsontothewall.
5.3.3. Positioning of signal transmitters
For automatic control of the connected pump,
acorrespondinglevelcontroldevicemustbe
installed. This needs to be provided by the cus-
tomer.
Float switches may be used as signal transmitters.
Connection of level sensors or electrodes is not
possible!Thecorrespondingsignaltransmitters
must be installed according to the unit's installa-
tion plan.
DANGER - explosive atmosphere!
If the connected signal transmitters are used
in potentially explosive areas, there is adan-
ger of fatal injuries from explosions! Thecon-
nected signal transmitters must always be
used outside of potentially explosive areas.
Installation must always be carried out by
aqualied electrician.
Notethefollowing:
Whenusingoatswitches,ensurethatthesecan
move freely in the operating space (pump cham-
ber, reservoir).
The water level of the connected pump must not
fall below the minimum.
Themaximumswitchingfrequencyofthecon-
nectedpumpmustnotbeexceeded.
5.4. Electrical connection
POTENTIALLY fatal danger due to electrical
voltage!
Incorrect electrical connections can cause fa-
tal electric shocks. Electrical connections may
only be carried out by aqualied electrician
approved by the local energy supply company,
in accordance with locally applicable regula-
tions.
DANGER - explosive atmosphere!
If the connected pump and signal transmitter
are used in potentially explosive areas, there
is adanger of fatal injuries from explosions!
Theconnected pump and signal transmitter
must always be used outside of potentially
explosive areas. Installation must always be
carried out by aqualied electrician.
NOTE
Depending on the system's impedance and the
connectedconsumers'max.no.ofconnections/
hour,voltageuctuationsorvoltagedropsmay
occur. Always have the electrical connections
carried out by an electrician authorised by the
local energy supply company.
Observe the installation and operating in-
structions for the connected pump and signal
transmitters.
The mains connection current and voltage must
be as stated on the rating plate.
All-pole disconnecting, K-type circuit breakers
must be installed!
Max.fuseprotectiononmainsside:25A(16Afor
S version with shock-proof/CEE16 plug)
Onswitchgearswithoutapowersupplysepa-
rationdevice(Oversion:withoutmainswitchor
plug) this must be provided by the customer!
Itisrecommendedaresidual-current-operated
protection switch (RCD, type A, sinus wave-form
current) be installed. Observe the local laws and
regulations on this too!
Route the power supply cable in accordance with
the valid norms and regulations and according to
the wiring diagram.
Ground the system (switchgear and all electric
consumers) in accordance with the regulations.
Fig. 2.: Overview of individual components
A Switchgear with main switch
W Switchgear with plug
C Switchgear without main switch and plug
1 Main switch 6 DIP switch 2
2 Motor contactor 7
Potentiometer for fol-
low-up time
3 Terminal strip 8
Rechargeable battery
installation location
4 Earth terminals 9 Mains terminal strip
5 DIP switch 1
5.4.1. DIP switch
The switchgear has two DIP switches. These are
usedtoswitchvariousfunctionson/off:
DIP switch 1, above the potentiometer
This DIP switch is used to adjust the rated current
for motor protection as well as activating or deac-
tivating the pump kick function and the internal
buzzer.
DIP switch 2, under the potentiometer
This DIP switch is used to select the mains voltage
(standardversionand"O"versiononly),tostipu-
late the service intervals. activate/deactivate the
connected pumps and to monitor the operating
parameters (S version only).
5.4.2. Switchgear mains connection - with main
switch
Insert the cable ends of the power supply cable
laid on-site through the threaded cable connec-
tions and secure them accordingly.
Connect the wires to the main switchasfollows:
Mainsconnection1~230V:
Cable:3-core
Terminals:4/T2(L),N(N)
The protective earth conductor (PE) is connect-
ed to the earth terminal (;).
DIPswitch2:DIPposition"1":OFF(bottom
position)

Related product manuals