EasyManua.ls Logo

Wilo Control MS-L 2x4kW Series - Standards and CE Marking; Product Description; Intended Use and Fields of Application; Set-up Overview

Wilo Control MS-L  2x4kW Series
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30 WILOSE04-2015V05DINA4
English PRODUCT DESCRIPTION
Pushbuttons and LEDs on the housing are used
to operate the switchgear, display the operating
state,andsignalfaults.Thehousingcovermust
not be opened during operation.
DANGER due to electrical voltage!
There is arisk of fatal electric shocks oc-
curring when performing work on the open
switchgear. Only operate the switchgear with
the cover closed!
2.5. Standards and guidelines used
The switchgear is subject to various European
directives and harmonised standards. See the EC
declaration of conformity for precise information
about these.
Also,variousregulationsareusedasabasis
for operating, installation and dismantling the
switchgear.
2.6. CE marking
The CE marking is attached to the rating plate.
3. Product description
The switchgear has been manufactured with
great care and is subject to constant quality con-
trols. Trouble-free operation is guaranteed if it is
installed and maintained correctly.
3.1. Intended use and elds of application
DANGER - explosive atmosphere!
If the connected pump and signal transmitter
are used in potentially explosive areas, there
is adanger of fatal injuries from explosions!
Theconnected pump and signal transmitter
must always be used outside of potentially
explosive areas. Installation must always be
carried out by aqualied electrician.
The MS-Lift switchgear is designed for
automaticcontrolof2nonEx-ratedpumpsin
lifting units and sewage chambers for water/sew-
age conveyance.
The switchgear must not
beinstalledinpotentiallyexplosiveareas.
beooded.
Intended use also includes observation of these
instructions. Any other use is considered to be
outside the intended use.
NOTE
Forautomaticcontrol,oatswitchesmustbe
provided by the customer.
3.2. Set-up
Fig. 1.: Overview of operating components
1 Main switch 3
Control panel with
buttons
2 LED indicators
The switchgear comprises the following main
components:
Mainswitch:forswitchingtheswitchgearon/off
NOTE
The"S"versionhasnomainswitch.Aplugis
pre-assembled instead.
The"O"versionhasnomainswitchandnoplug.
Acorrespondingmainsdisconnectionfacility
must be provided by the customer in accord-
ance with the local regulations.
LEDs for displaying the current operating state
(operation/fault)
Automatic mode
Pump operation
High water
Service interval indicator
Overload fault
Winding fault
Monitoring of certain operating parameters
(version S only)
Control panel with buttons
Manual mode for each pump
Stop
Automatic mode
Buzzer OFF/reset
Contactor combinations for connecting up pumps
during direct starting, including electronic trig-
geringforexcesscurrentprotection
3.3. Function description
The microcontroller-controlled Micro Control
switchgearisdesignedforcontroloftwoxed
speed pumps with level-dependent switching.
Levelmeasurementisviaatwo-positioncontrol
withaoatswitchforeachpump,whichneeds
tobeprovidedbythecustomer.Thepumpis
activated/deactivated automatically depending
onthelllevel.Ifafollow-uptimeisrequired,
thiscanbesetviaapotentiometer.Pumpcycling
is carried out after every pumping procedure.
Onreachinghigh-waterlevel(detectedviaasep-
arateoatswitch),avisualandaudiblewarningis
emitted and forced switch-on of the pumps takes
place.Thecollectivefaultsignal(SSM)isactive.
The current operating state is indicated via LEDs
on the front side. Operation is via 5 pushbuttons
onacontrolpanelattachedattheside.
Faults are indicated visually via LEDs and audibly
viaanintegratedbuzzer.Thelasterrorisstoredin
the fault memory.
3.4. Technical data
3.4.1. Inputs
3digitalinputsforoatswitches(pumpbaseload
on/off, pump peak load on/off, high water)
2 inputs for thermal winding monitoring with
bimetallic temperature sensor. Connection of PTC
sensors is not possible!
3.4.2. Outputs
1 potential-free contact for SSM

Related product manuals