10 Faults, causes and remedies
The troubleshooting must only be carried out by a qual-
ified specialist, and work on the electrical connection
must only be carried out by a qualified electrician.
10.1 Fault signals
The fault signal LED indicates a fault.
The pump switches off (depending on the fault) and
attempts a cyclical restart.
Faults Causes Remedy
Pump is not
running
although the
power supply is
switched on
Electrical fuse
defective
Check fuses
No voltage supply
at pump
Rectify the power interruption
Noisy pump
Cavitation due to
insufficient suction
pressure
Increase the system pressure within
the permissible range
Check the delivery head and set it to
a lower head if necessary
Building does
not warm up
Thermal output of
the heating surfaces
is too low
Increase setpoint
Change the control mode from Δp-c
to Δp-v
LED Faults Causes Remedy
Lights
up red
Blocking Rotor blocked Activate manual
restart or contact
customer service
Contacting/
winding
Winding defective
Flashes
red
Under/overvoltage Power supply too
low/high on mains
side
Check mains
voltage and
operating
conditions, and
request customer
service
Excessive
module
temperature
Module interior too
warm
Short-circuit Motor current too
high