en Description
34 WILO SE 2020-02
Menu no. Parameter /
info
Min. Max. Text Default Unit Ac-
cess
level
Description
1.00
Setpoints 1 Sub menu for values related to the set-
ting of the setpoint
1.04
MPswitch-
on pressure
1.0 4.9 1.2 bar 1 Set pressure for switching on the MP
1.05
MPswitch-
off pressure
1.0 4.9 3,5 (HiM-
ulti3-24);
4,4 ( HiM-
ulti3-25);
4,9 ( HiM-
ulti3-45)
bar 1 Set pressure for switching off the MP de-
pend on selected curve in menu 5.04;
Setpoint should be least 0,5bar higher
than switch-on pressure
1.06
MP stop
delay
1.0 120 20 s 2 The delay to stop a pump after stop
threshold is reached and current value
stays above
1.18
CP start
time
-60 +60 20 s 2 Start time related to start of MP
1.19
CP stop time -60 +60 +2 s 2 Stop time related to start of MP
1.25
Pressure
jump in
TWM
-0.7 +0.7 +0.2 bar 2 Defines the different of switch-off pres-
sure between TWM and RWM
1.26
Delay for re-
duced
switch-off
pressure
0 300 30 s 2 To protect the pump when it is running
and the pump do not reach the switch-
off pressure any more, it can be adjust a
time in menu 1.26 after that the switch-
off pressure will be reduced.
Defines the time after switch-off pres-
sure will reduced by adjusted value in
menu 1.27
1.27
Reduced
pressure
rating
0 1.0 0.2 bar 2 Defines the pressure rating by which
switch-off pressure will reduced after
delay time in menu 1.26.
Menu no. Parameter /
info
Min. Max. Text Default Unit Ac-
cess
level
Description
2.00
Communic-
ation set-
tings
1
3.00
Operation 1 The mode for the panel, pumps and
valves if included
3.01
Drives OFF
ON
OFF 1 The mode of panel can be drives either on
or off
3.02
MP mode OFF
Man
Auto
Auto 2 The mode of MP can be manual off,
manual on or automatic
3.03
CP mode OFF
Man
Auto
Auto 2 The mode of CP can be manual off,
manual on or automatic
3.06
Three way
valve mode
Rain water
Tap water
Auto
Auto 1 The mode of 3-way valve can be manual
for RWM, manual for TWM or automatic
3.10
Running
time MP
manual
mode
0 180 120 s 2 Running time of MP in manual mode;
after running time the MP mode will be
OFF; 0s means unlimited running time