Description en
Installation and operating instructions Wilo-RAIN3 35
Menu no. Parameter /
info
Min. Max. Text Default Unit Ac-
cess
level
Description
3.11
Running
time CP
manual
mode
0 180 120 s 2 Running time of CP in manual mode; after
running time the CP mode will be OFF; 0s
means unlimited running time
Menu no. Parameter /
info
Min. Max. Text Default Unit Ac-
cess
level
Description
4.00
Information 1 The current operating values of panel and
pumps
4.02
Current
pressure
value
0.0 10.0 bar 1 The current pressure as reported from the
pressure sensor
4.04
Current
valve states
Rain water Tap wa-
ter; Auto
1 The state of installed valves can be shut,
open or automatic
4.08
Current wa-
ter level
rainwater
storage tank
0 1000 cm 1 The current level of rainwater in the rain-
water storage tank
4.09
Current wa-
ter capacity
rainwater
storage tank
0 100 % 1 The calculated value of water capacity in
cistern if shape of the rainwater storage
tank is specified in the menu
4.12
Total run-
ning time of
the panel
0 0429
4967
295
0 h 1 Total operating time. Time pulse in back-
ground counts in minutes unlike the dis-
play unit.
4.13
MP running
time
0 6553
5
0 h:mi
n
1 Operating time of MP
4.14
CP running
time
0 6553
5
0 h:mi
n
1 Operating time of CP
4.17
Total cycles
of panel
0 6553
5
0 1 The number of power-on cycles for the
panel
4.18
MP switch
cycles
0 6553
5
0 1 The number of power-on cycles for MP
4.19
CP switch
cycles
0 6553
5
0 1 The number of power-on cycles for CP
4.22
Switchgear
serial num-
ber
0 9999
9999
9
0 1 ID of the panel
4.24
Software
version
0 9999 V5.000 1 The software version of the installed ap-
plication
Parameters such as the rainwater storage tank dimensions have to be set in this
menu
Menu no. Parameter /
info
Min. Max. Text Default Unit Ac-
cess
level
Description
5.00
Installation 1 The settings regarding the installation of
the panel in a system
5.04
Pump type HiMulti3-24; HiM-
ulti3-25; HiM-
ulti3-45
Last setting
will be used
3 Select of pump type to define pump
curves to get optimized set pressure for
switch-off refer in menu 1.05
5.05
Number of
CP
0 1 0 2 Contains the number of pumps dedicated
to a cistern