EasyManua.ls Logo

Wilo VeroLine-IP-E Series - Page 40

Wilo VeroLine-IP-E Series
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English
Installation and operating instructions Wilo-VeroLine-IP-E, VeroTwin-DP-E 91
5.2.3.0 Bus address Setting of bus address
5.2.4.0 IF gateway val A
Specific settings of the IF-Mod-
ule, depends on protocol type
Further information can be
found in the installation and
operating instructions of the
IF-Modules.
5.2.5.0
IF gateway val C
5.2.6.0 IF gateway val E
5.2.7.0 IF gateway val F
5.3.0.0 In1 (sensor input) Settings for sensor input 1 Not displayed in the manual
control mode (incl. all sub-
menus)
5.3.1.0
In1 (sensor value
range)
Display of sensor value range 1
Not displayed with PID control
5.3.2.0 In1 (value range) Setting of the value range
Possible values: 0...10 V/2...10 V/
0...20 mA/4...20 mA
5.4.0.0 In2 Setting for external setpoint
input 2
5.4.1.0 In2 active/inactive ON
External setpoint input 2 active
OFF
External setpoint input 2 inac-
tive
5.4.2.0 In2 (value range) Setting of the value range
Possible values: 0...10 V/
2...10 V/0...20 mA/4...20 mA
Not displayed when In2 =
inactive
5.5.0.0
PID parameters Settings for PID control Only displayed when PID
control is active (incl. all sub-
menus)
5.5.1.0
P parameter Setting of the proportional term
of the control
5.5.2.0 I parameter Setting of the integral term of
the control
5.5.3.0 D parameter Setting of the derivative term of
the control
5.6.0.0 Fault Settings for behaviour in case of
error
5.6.1.0 HV/AC HV “heating” mode
AC “cooling/air-conditioning”
mode
5.6.2.0 Emergency opera-
tion speed
Display of emergency operation
speed
5.6.3.0 Auto reset time Time until automatic acknowl-
edgement of an error
5.7.0.0 Other settings 1
5.7.1.0 Display orientation Display orientation
No. Designation Type Symbol Values/explanations Display conditions
±
±
±
±
±
±
±
±
±
±
±
±
±
±

Related product manuals