36 WILO SE 01/2009
2.31 FTS valve After-sales service password is required
Setting of the running time tolerance of the software when
opening the valve
000 – 100 sec 20 sec
> 020 sec <
2.32 FTS valve O After-sales service password is required
Setting of the running time tolerance of the software when
closing the valve
000 – 100 sec 30 sec
> 030 sec <
2.40 sensor type After-sales service password is required
Selection of the type of pressure sensor
6 bar
10 bar
10 bar
> 10.0 bar <
2.45 P Δp-off DW After-sales service password is required
Setting of the differential for pump switch-off in potable
water operation. The set pressure for switching off the pump
(menu 2.13) in rainwater operation together with the differ-
ential set here must be at least 0.5 bar greater than the set
pressure for switching on the pump (menu 2.12).
(For pump switch-off set pressure in rainwater operation, see
menu 2.13)
- 0.7 – +0.7 bar,
(menu 2.13 +
menu 2.45 at least
0.5 bar greater
than menu 2.12)
+0.2 bar
> x.x + 0.2 bar <
2.46 p dry run. After-sales service password is required
Setting of a minimum pressure threshold for dry-running
detection
0.7 – 1.0 bar 1 bar
>1.0 bar <
2.50 choice-stop Password 02 is required
Display of switch-off logic adapted as appropriate to the
pump. F1 = 4 means switch-off pressure of 4 bar for the MC
304 pump.
F1 = 0
F1 = 4
F1 = 5
F1 = 9
F1 = 4
(Display of infor-
mation only)
> F1 = 4 <
2.51 t p compare After-sales service password is required
Setting of the running time for pressure comparison
10 – 120 sec 30 sec
> 030 sec <
2.52 p jump After-sales service password is required
Setting of the pressure change increment
0.1 – 0.5 bar 0.2 bar
>0.2 bar <
2.53 p off var. Password 02 is required
Display of the variable pressure for pump switch-off.
The value is calculated as follows:
set pressure for pump switch-off (menu 2.13) + pressure
change increment (menu 2.52)
(Menu 2.13 +/-
menu 2.52)
4.0+x.x bar
(MC 304)
(Display of infor-
mation only)
>4.0 ± x.x bar <
2.54 p actual Password 02 is required
Display of the actual pressure at the pressure sensor
Currently meas-
ured pressure
x.x bar
(Display of infor-
mation only)
>2.2 bar <
2.99 back with OK Return to the main menu Confirmation with
“OK” button
3Pump Nomi-
nal Values
Main menu: Pump Nominal Values
3.01 pump operat Display of the number of hours that the pump has been in
operation
xxxxxxx.xx h
(Display of infor-
mation only)
> 0000123,00 h <
3.02 tank operat Display of the number of hours of operation with rainwater xxxxxxx.xx h
(Display of infor-
mation only)
> 0000103,00 h <
3.03 topup water Display of the number of hours of operation with potable
water
xxxxxxx.xx h
(Display of infor-
mation only)
> 0000020,00 h <
3.99 back with OK Return to the main menu Confirmation with
“OK” button
Menu Description Parameters Factory settings