INSTRUCTION MANUAL
UNIT AIR HEATER
TYPE TR
Production from 2019
THIS DOCUMENT MUST ABSOLUTELY BE READ BEFORE STARTING THE
INSTALLATION.
INSTRUCT USER AND LEAVE THIS DOCUMENT WITH HEATER FOR
REFERENCE.
Date: 01-02-2019
Instruction manual version TR-GB-4001-a
Heaters for GB

Other manuals for Winterwarm TR

Questions and Answers

  • R
    ruizrobinAug 16, 2025
    What to do if Winterwarm TR Heater has too many flame failures while burning?
    • D
      Danielle MedinaAug 17, 2025
      If your Winterwarm Heater experiences too many flame failures while burning, it could be due to several reasons. The gas supply might not be constant, leading to a drop in gas supply pressure. Check the gas supply pressure while the heater is burning. Alternatively, the burner pressure for Low fire may be too low, causing the flame to extinguish. Check the burner pressure at Low fire and adjust if necessary. Another possibility is recirculation of flue gas. Inspect the flue system and fresh air supply, ensuring that only certified, original parts are used.
  • L
    Lisa MontoyaAug 19, 2025
    What to do if Winterwarm TR heat exchange sensor or flue sensor is overheated?
    • O
      omcgrathAug 19, 2025
      If the heat exchange sensor or flue sensor is overheated in your Winterwarm Heater, verify that the connectors J12 and J6 are correctly plugged in and that the connection J12[1-4] (optional overheating protection) is closed. Also, check if the system fan supplies enough air. Finally, review the settings of the gas valve, as the heater may be overfired; if so, adjust the burner pressure.
  • S
    Sarah WallaceAug 22, 2025
    What to do if Winterwarm TR has no flame after ignition?
    • J
      Janet RothAug 22, 2025
      If there is no flame after ignition in your Winterwarm Heater, it could be due to insufficient gas pressure. The gas mixture may also be too poor; in this case, adjust the gas valve. Check if the gas valve opens by checking for a 230 V voltage on the valve during ignition. Also, check if the ignition electrode sparks. If it does not, inspect the cable and electrode, replacing them if damaged. Finally, check the burner control unit and replace it if it does not give a spark output.
  • A
    Amy HodgesAug 25, 2025
    What to do if Winterwarm TR flame lasts only 5 seconds after ignition?
    • B
      Beth SotoAug 25, 2025
      If the flame lasts only 5 seconds after ignition in your Winterwarm Heater, check the ignition/ionisation cable and the electrode, ensuring the cable has a resistance of 1 kΩ. Also, ensure that the air heater is properly earthed. If these steps do not resolve the issue, the circuit board may be defective.
  • J
    Joyce Abbott MDAug 27, 2025
    What to do if Winterwarm TR Heater has insufficient air passage through the heat exchanger?
    • A
      Ashley CruzAug 27, 2025
      If your Winterwarm Heater has insufficient air passage through the heat exchanger, and the pressure switch does not close, start by checking if the combustion fan is running. Next, verify if the flue system is blocked or restricted. Also, inspect the pressure switch and its connections. Finally, examine the heat exchanger for flue leakage.
  • S
    Scott MooreAug 30, 2025
    What to do if Winterwarm TR Heater heat exchange sensor or flue sensor not detected, or short circuit?
    • A
      Albert WilkersonAug 30, 2025
      If the heat exchange sensor or flue sensor is not detected or shows a short circuit in your Winterwarm Heater, it may be due to differing readings between the two internal sensors of the heat exchange sensor. Measure the resistance of each sensor, looking for approximately 10 KΩ at 20 °C. If the measured values differ too much, replace the sensor.
  • I
    Ian RochaSep 2, 2025
    What to do if Winterwarm TR Heater has too many reset actions in a short timespan?
    • T
      Tony WillisSep 2, 2025
      If your Winterwarm Heater indicates too many reset actions in a short timespan, this error should disappear after some time or if the main power is disconnected for a while.
  • P
    pdunnSep 4, 2025
    What to do if Winterwarm TR Heater has an internal error?
    • P
      Philip MartinSep 5, 2025
      If your Winterwarm Heater shows an internal error, isolate the electrical supply and reenergise it. If this does not resolve the issue, replace the burner control unit.
  • S
    Steven SnyderSep 7, 2025
    What to do if Winterwarm Heater has an E-error for more than 24 hours?
    • A
      albertgeorgeSep 7, 2025
      If your Winterwarm Heater displays an E-error for more than 24 hours, switch the air heater off and on, and then check the error code.
  • L
    Lisa GonzalezSep 10, 2025
    Why Winterwarm Heater pressure switch is closed in stand-by mode?
    • L
      Luis HaleSep 10, 2025
      If the pressure switch is closed in stand-by mode in your Winterwarm Heater, check if the contact is stuck and replace the pressure switch if necessary. Also, check if there is water in the hose and dry the hose if needed.

Winterwarm TR Specifications

General IconGeneral
Power2000W
Voltage220-240V
CategoryHeater
Heating Area20m²
Safety FeaturesOverheat protection