Installation manual
Air heater
Type XR+

Questions and Answers

  • S
    shawn80Aug 18, 2025
    What to do if the Winterwarm Heater burner fan does not work?
    • L
      Laura NelsonAug 18, 2025
      If the burner fan in your Winterwarm Heater isn't working, start by checking if it's blocked. Next, inspect the wiring for any damage. If neither of these is the problem, the burner fan itself may be defective and require replacement.
  • T
    Timothy DouglasAug 20, 2025
    What to do if my Winterwarm Heater shows E-error for more than 24 hours?
    • M
      Michael KingAug 20, 2025
      If your Winterwarm Heater displays an E-error for more than 24 hours, switch the air heater off and on and check the error code.
  • P
    Philip OrtizAug 23, 2025
    What to do if my Winterwarm Heater has an internal error?
    • E
      ericcontrerasAug 23, 2025
      To address an internal error in your Winterwarm Heater, first, isolate the electrical supply and then reenergize it. If the problem persists, replace the burner control unit.
  • B
    Bradley TorresAug 26, 2025
    What to do if the Winterwarm Heater has no flame after ignition?
    • S
      Stephen MccoyAug 26, 2025
      If your Winterwarm Heater doesn't ignite, several factors could be at play. First, ensure there's sufficient gas pressure. If that's not the issue, the gas mixture might be too lean; in this case, adjust the gas valve according to section 8.1. Also, verify the gas valve is opening by checking for a 230 V voltage during ignition. Finally, check if the ignition electrode sparks. If it doesn't, inspect the cable and electrode for damage, replacing them if necessary. If the electrode sparks, the burner control unit might be faulty and need replacement.
  • M
    Mrs. Jennifer Hernandez MDAug 28, 2025
    What to do if the Winterwarm Heater flame lasts only 5 seconds after ignition?
    • D
      david11Aug 28, 2025
      If the flame in your Winterwarm Heater only lasts for 5 seconds after ignition, check the ignition/ionisation cable and the electrode, ensuring the cable has a resistance of 1 kΩ. Also, ensure the air heater is properly earthed. If these steps don't resolve the issue, the circuit board might be defective.
  • S
    Sydney BanksAug 30, 2025
    What to do if the Winterwarm Heater has too many flame failures while burning?
    • E
      Elizabeth PriceAug 30, 2025
      If your Winterwarm Heater experiences frequent flame failures during operation, it could be due to a few reasons. One possibility is an inconsistent gas supply, leading to pressure drops. Another is the burner pressure for Low fire being too low, causing the flame to extinguish prematurely. Lastly, check for recirculation of flue gas, where flue gas is drawn back into the air inlet due to a flue terminal issue, resulting in a lack of oxygen.
  • A
    allenmyersSep 2, 2025
    What to do if the Winterwarm Heater heat exchange sensor or flue sensor is overheated?
    • J
      Jeffrey HudsonSep 2, 2025
      If the heat exchange sensor or flue sensor in your Winterwarm Heater is overheating, first check if the connectors J12 and J6 are correctly plugged in and if the connection J12[1-4] (optional overheating protection) is closed. Then, check if the system fan is supplying enough air. Finally, review the gas valve settings to ensure the heater isn't overfired; if it is, adjust the burner pressure.
  • F
    fvegaSep 4, 2025
    What to do if the Winterwarm Heater pressure switch is closed in stand-by mode?
    • L
      Lisa DavisSep 4, 2025
      If the pressure switch in your Winterwarm Heater is closed while in stand-by mode, check if the contact is stuck and replace the pressure switch if necessary. Also, check if there is water in the hose and dry the hose if needed.
  • B
    Brittany HughesSep 7, 2025
    What to do if Winterwarm Heater has insufficient air passage through the heat exchanger?
    • N
      Nathan NguyenSep 7, 2025
      If there's insufficient air passage through the heat exchanger in your Winterwarm Heater, and the pressure switch doesn't close, verify that the combustion fan is running. Also, check if the flue system is blocked or restricted. Inspect the pressure switch and its connections. Finally, check the heat exchanger for flue leakage.
  • D
    diamond73Sep 9, 2025
    What to do if the Winterwarm Heater flame detected after closing the gas valve?
    • B
      blowerySep 9, 2025
      If a flame is detected in your Winterwarm Heater after the gas valve closes, check if the gas valve closes too slowly and replace it if necessary. Also, check if the ionisation electrode is wet and dry, clean, or replace the electrode if needed.

Summary

2. Safety Instructions

2.1. Installation Safety

Emphasizes installation by authorized personnel and compliance with regulations.

4. Installation

4.1. Installation Preparation

Outlines pre-installation checks including data badge verification and space requirements.

4.2. Heater Positioning and Suspension

Specifies requirements for locating the heater, including clearance, distance, orientation, and suspension options.

4.4. Electrical Connection

4.5. Room Thermostat

4.5.2. Modulating Thermostat Installation

Explains how to connect an MTS or MTC thermostat to the air heater.

5. Flue Systems

5.1. Compatible Flue Terminals

Lists compatible flue terminals for vertical discharge with article numbers.

5.1. Flue Terminals

5.2. Maximum Flue Length

Details maximum straight flue lengths for horizontal and vertical orientations, considering bends.

5.3. Condensate in Flue System

5.4. Flue Terminal Installation

5.4.1. Roof Terminal Installation

Details the preparation and steps for installing a roof flue terminal.

5.4.2. Wall Terminal Installation

5.4.3. Flue System Parts Installation

5.4.3.4. General Flue Installation

6. Operating the Air Heater

6.5. Overheating Protection

6.6. Flue Passage Check

Describes the pressure switch function for checking combustion air passage.

7. Commissioning the Air Heater

7.1. Setting Adjustments

Outlines checks and adjustments needed for proper combustion efficiency after installation.

7.2. Commissioning Procedure

Guides the process of commissioning the air heater after installation.

8. Combustion Settings

8.1. Adjusting Burner Settings

Details how to adjust gas valve settings for high and low fire using a calibrated analyzer.

9. Troubleshooting

9.1. Volatile Lock Outs

Lists volatile lock-out errors that require manual reset.

9.2. Temporary Errors

Describes temporary errors that resolve automatically once the cause is fixed.

9.4. Troubleshooting Instructions

Case 1: Short Flame Detection

Addresses flame detection issues lasting only 5 seconds after ignition.

Case 2: No Flame After Ignition

Covers scenarios where no flame is detected after ignition.

Case 3: Sensor Overheating

Deals with overheating of heat exchange or flue sensors.

Case 4: Sensor Detection Failure

Addresses heat exchange or flue sensor not detected or short-circuit issues.

Case 16: Flame Before Gas Valve Opening

9.5. Further Troubleshooting

10. Maintenance

10.3. Burner Unit Maintenance

Details specific maintenance procedures for the burner unit, including electrode adjustment.

11. Electrical Wiring Diagram