C OOKTOP V ENTILATION R ECOMMENDATIONS
Chimney Wall Hoods CT15E CT15G CT30E/EU CT30G CT36E/EU CT36G IG15 IM15 IS15 IF15
CTWH30 215* 215* 450 450 400* 215* 215* 400*
CTWH36 215* 215* 600 600 600 600 400* 215* 215* 400*
Chimney Island Hood CT15E CT15G CT30E/EU CT30G CT36E/EU CT36G IG15 IM15 IS15 IF15
IH4227 215* 215* 600 600 600 600 400* 215* 215* 400*
Downdrafts CT15E CT15G CT30E CT30G CT36E CT36G IG15 IM15
DD30I 215* 215* 500 500 215* 215*
DD30R 215* 215* 900 900 215* 215*
DD36I 215* 215* 500 500 500 500 215* 215*
DD36R 215* 215* 900 900 900 900 215* 215*
Pro Series Hoods CT15E CT15G CT30E/EU CT30G CT36E/EU CT36G IG15 IM15 IS15 IF15
All Hoods 215* 215* 600 600 600 600 400* 215* 215* 215*
* Use these requirements to determine total CFM when installing multiple cooking products.
NOTE: Downdrafts are not recommended for use with Models CT30EU, CT36EU, IS15 or IF15.
CFM recommendations are based on total Btu/hr output. Wolf recommends 1 CFM per 100 Btu/hr (.03 kWh). Additional CFM may be
required for charbroilers, griddles and long duct runs.
CFM RECOMMENDATIONS