CRD-XP_2006-04_EN Subject to technical changes Page 3 of 16
2 Operation
Display
1 Set value adjustment enabled
2 Advanced level P00...P73
Defrost
Cool
Fan
Status LED Value/parameter number
Selecting parameters
1. Press the <P> key to display the parameter number.
The parameter number will appear in the display for as long as the key is depressed.
2. To select individual parameters with the <P> key depressed, press the ▲ or ▼ key.
When the key is released, the value corresponding to the parameter appears.
P
P
P
P
Parameter levels: Standard level and advanced level
The setting menu is divided into two distinct function areas, the standard level and the advanced level.
The standard level comprises parameters P00 to P09. In this area, all standard actual values can be
displayed and the basic set value for the controller can be set. Parameter P09 can trigger a manual
defrost if required.
The advanced level comprises both parameters P00 to P09 and also parameters P10 to P70. In this
area, all control, defrost, fan, compressor and probe parameters can be displayed and set.
Within a level, you can toggle between the parameters with one single operating function.
Enabling the advanced level
1. To switch to the advanced level, press the <P> key for 5 seconds.
The LED "Advanced level" will flash for as long as the level is enabled.
P
...
P
...
5 secs.
2. To return to the advanced level, press the <P> key again for 5 seconds.
If no key is pressed within 2 minutes, the display automatically returns to the standard level. The
return is always to the temperature display which is defined by parameter P60.
P
1