8
NOTE: For error conditions not shown above, disconnect Freedom Remote Control Panel for 30 seconds, verify that phone
cable is plugged in at remote and inverter/charger and verify that batteries are above 10 VDC. If condition presists, discon-
nect incoming AC power from inverter/charger and remove positive battery lead for 30 seconds.
LED Indication Fault LED Error Detected Possible Solution
OVERTEMP On OFF Over-temperature shutdown. Increase air circulation and allow to cool.
BATTERY STATE ON Low Battery Shutdown. Charge batteries.
Empty blinking (too low to continue inverting)
BATTERY STATE ON Battery Overload. Select lowest Power Share setting. Turn off
Empty On (excessive ripple voltage during charge) DC Loads. Restart Charger.
15.5 VDC blinking ON High battery shutdown. Check other charging sources connected to
(31.0 VDC in 24 V system) the battery.
AC IN blinking ON AC Backfeed Disconnect Incoming AC power and correct
(external AC power detected at inverter wiring.
output).
INVERT blinking ON Inverter overload Reduce AC load on inverter. Reset by pressing
(too much AC load on inverter). INVERT Off and On.
CHARGE blinking ON Charger overload Check batteries. Turn Off all DC loads.
(Battery voltage too low to charge). Restart charger.