Default Settings and Ranges
975-0240-01-01 B–5
Grid Support Menu
Gen Support Menu
Item
Default Range
Step Size24 V 48 V 24 V 48 V
Grid Supp Volts 27.0V 54.0V 23.0–29.0V 46.0–58.0V 0.1V
Max Sell Amps 27A
0–60A
a
a.This setting is restricted to the selected AC1 breaker size.
1A
Load Shave Amps 48A 0–48A 1A
Load Shave Start
b
b.When Load Shaving is enabled, if Load Shave Start and Load Shave Stop are
set to the same time, the XW Inverter/Charger load shaves continuously.
n/a 12:00 AM–11:59 PM,
00:00–23:59
n/a
Load Shave Stop n/a 12:00 AM–11:59 PM,
00:00–23:59
n/a
Setting Default Range Step Size
GenSupp Mode Disabled Enabled, Disabled n/a
GenSupp Amps 10A 4–48A 1A